文章以一起110 kV瓷套式电缆终端漏油发热缺陷为研究对象,结合带电检测技术,通过解体检查及应力锥材料检测,排除了材料本身引起缺陷的可能性;基于终端结构及漏油发热原理,系统分析了漏油发热缺陷的原因。研究发现,缺陷根源在于封铅工艺不良,导致电缆内部受潮,在长时间运行下产生局部放电,引起应力锥烧蚀并出现裂口,最终造成终端漏油发热问题。针对该问题,提出了加强设备全寿命周期管理、深化带电检测及在线监测技术应用等防范措施,为高压电缆施工质量管控及运维管理提供了重要技术参考。
Taking an oil-leakage and heating defect in a 110 kV bushing-type cable terminal as the research object
combining it with live detection technology
this study eliminates the possibility that the defect is caused by the material itself through disassembly inspection and stress cone material detection. Based on the terminal structure and the mechanisms of oil-leakage and heating
the causes of the oil-leakage and heating defect are systematically analyzed. The study reveals that the root cause of the defect is poor lead sealing workmanship
which leads to moisture ingress into the cable. During long-term operation
partial discharge is generated
resulting in ablation and cracks on the stress cone
and ultimately causing the oil-leakage and heating of the terminal. In view of this problem
preventive measures are put forward
including strengthening the full-life cycle management of equipment and deepening the application of live detection and online monitoring technologies
which provide an important technical reference for the construction quality control and operation management of high-voltage cables.
刘云龙,邵愚,黄会贤,等.110 kV电缆复合套管终端漏油缺陷分析[J].Electric Engineering,2019(7):62-64.
范在乾,咸日常,冷学冰,等.35 kV XLPE电力电缆终端结构参数优化[J].绝缘材料,2023,56(11):73-79.
Su D.Silicone rubber thermal aging performance for cables and accessories[J].Journal of Materials Science: Materials in Electronics,2024,35(5):328.
段建家,王海跃,岳一石,等.电缆故障导致变电站多条出线跳闸 原因分析[J].湖南电力,2016,36(5):61-64.
张瑞敏,张沛红,宋淑伟,等.界面空间电荷对高压直流电缆终端电场分布的影响[J].高电压技术,2019,45(6):1762-1766.
朱晓辉,李斌,梁瑞成,等.高压电缆设备终端的分类及其选型原则[J].高压电器,2007,50(4):315-317.
罗真海,陆国俊,王晓兵,等.高压电缆瓷套式终端发热原因[J].高电压技术,2007,33(11):240-241,244.
Chen S,Xia Y,Shao X,et.al.Cause Analysis and Countermeasure of Oil Leakage Caused by Cable Terminal Belt Expansion[C],2019 IEEE 3rd Conference on Energy Internet and Energy System Integration (EI2),Changsha,China,2019: 2338-2341.
Liu Z. W.,Li J. L.,Zhang T. Y.,et al.Accurate identification of partial discharge signals in cable terminations of high-speed electric multiple unit using wavelet transform and deep belief network[J].Applied Sciences,2024,14(11):4743.
陈杰,吴世林,胡丽斌,等.退役高压电缆附件绝缘状态及理化性能分析[J].电工技术学报,2021,36(12):2650-2658.
刘宏达,祁铭东,丁阳,等.基于接地回路电阻检测法的高压电缆接地故障诊断技术研究与应用[J].山东电力高等专科学校学报,2026,29(1):1-8.
苏宁.基于红外图像的高压电缆终端故障诊断技术研究[D].淮南:安徽理工大学,2025.
马超,李宁,李新平,等.基于红外热成像的电缆终端漏油缺陷检测机理分析[J].南方电网技术,2021,15(5):58-63.
0
浏览量
0
下载量
0
CSCD
关联资源
相关文章
相关作者
相关机构
京公网安备11010802024621