1. 中国电力工程顾问集团西南电力设计院有限公司
2. 国网经济技术研究院有限公司
纸质出版:2025
移动端阅览
蒲凡, 李林, 侯中伟, 等. 高海拔特重冰区特高压交流耐张铁塔选型研究[J]. 电力勘测设计, 2025,204(2):38-42.
蒲凡, 李林, 侯中伟, 等. 高海拔特重冰区特高压交流耐张铁塔选型研究[J]. 电力勘测设计, 2025,204(2):38-42. DOI: 10.13500/j.dlkcsj.issn1671-9913.2025.02.007.
DOI:
高海拔特重冰区特高压交流铁塔尺寸大、负荷重,塔型选择是否合理直接影响到铁塔受力的合理性和结构的安全性,现有的铁塔设计经验已不能满足要求。本文对典型耐张塔,包括干字型塔、酒杯型塔、门型塔以及分体塔的受力特点进行分析,按照3 000 m海拔的跳线间隙进行尺寸规划,对40 mm和60 mm特重冰区各型铁塔进行了建模计算,从经济性、地形适应性和节点构造难度等方面给出了推荐的塔型选择方案,为铁塔设计和工程建设提供参考。
The size and load of UHV AC tower in the high altitud and extra heavy ice zone is large
so whether the tower type is reasonable or not directly affects the rationality of the force and the safety of the structure of the towers
and the existing tower design experience can’t meet the requirements.In this paper
the mechanical characteristics of typical tension towers
including gan-type tower
cup-type tower
door-type tower and fission tower are analyzed
the size is planned according to the jumper clearance at 3 000 m altitude
modeling and calculation of different type of towers in 40 mm and 60 mm extra heavy ice zone are carried out
the recommended tower type selection scheme is given from the aspects of economy
terrain adaptability and joint construction difficulty
the research results can provide reference for tower design and engineering construction.
0
浏览量
19
下载量
CSCD
关联资源
相关文章
相关作者
相关机构