Wind load is the main control load of transmission tower
and the value of damping ratio directly affects the design value of wind load of transmission tower
the damping ratio of transmission tower is of great significance for wind resistant design of transmission lines. According to GB 5009—2012
the standard 0.01 of steel structure is generally used for the damping ratio of transmission towers. To accurately study the dynamic parameters of the transmission tower
two 110 kV transmission towers with the same structure
transmission tower and tower-line system
are tested to get the excitation response and dynamic parameters precisely. The vibration signals are obtained by using 4 different excitation methods
modified periodogram algorithm is used to denoise the response signals
half-power bandwidth method is applied to identify the dynamic parameters of response signals. The finding indicated that the ambient excitation can meet the requirements of the identification accuracy of damping ratio. Under the condition of slight vibration
whether suspend wire or not has almost no influence on the value of the damping ratio along the cross arm direction
and the value of the damping ratio of the tower-line system along the conductor direction is 20% less than that of the single tower.