This paper presents a systematic review of optimal transformer configuration in weak sending-end distribution networks with high renewable energy penetration. As the primary equipment for voltage transformation and power flow aggregation
transformers face new challenges in their capacity sizing
location selection
tap-changer setting
and number determination under weak-grid conditions. The review is organized around two parallel dimensions: a physical-problem-oriented dimension and a mathematical-method-oriented dimension. From the physical perspective
five key challenges specific to transformer configuration are identified: strong voltage-reactive power coupling
stability constraints under weak-grid conditions
temporal capacity sizing difficulties
multiple sources of uncertainty
and combinatorial explosion from discrete decision variables. The impact of each challenge on the four transformer configuration dimensions (capacity
turns ratio
location
and tap position) is analyzed in detail. From the mathematical perspective
existing approaches are comparatively examined across model formulation
optimization solution
and decision evaluation
with particular emphasis on algorithm suitability for the mixed-integer nature of transformer configuration (discrete tap positions and unit numbers combined with continuous capacity variables). By cross-mapping the two dimensions
a problem-method maturity matrix is developed to identify research gaps and emerging topics. The results indicate that transformer configuration method selection essentially involves a trade-off among modeling accuracy
solvability
and scalability. Existing studies predominantly concentrate on convexifiable problems
whereas scenarios involving implicit nonconvex weak-grid stability constraints in transformer configuration remain insufficiently investigated. Future research should prioritize refined embedding of stability constraints into transformer configuration models