换流变压器实际运行中受谐波激励影响,其损耗与温升相较基波额定工况显著升高,对设备长期运行稳定性构成严峻挑战。首先,依据换流变压器实际结构参数,构建三维仿真模型,获取基波与谐波工况下变压器磁通密度分布及损耗特性;搭建热-流耦合仿真模型,揭示变压器温度场与流场的分布规律,结果表明计入谐波后变压器损耗及绕组热点温度均显著上升。其次,在油箱壁面增设电屏蔽和磁屏蔽装置开展损耗抑制效果研究,磁屏蔽效果更为突出;在此基础上,分析屏蔽装置长度、厚度和高度对油箱损耗的影响规律,采用响应面法结合满意度函数构建多目标优化模型,对参数进行全局优化,优化后油箱壁面总损耗和绕组热点温度均显著降低。最后,基于优化后的换流变压器油箱壁面进行分域取点,计算各区域测点与绕组热点温度的相关性,引入GA-BP神经网络模型对高相关性的点进行反演。结果显示,对不同组合的高相关性测点进行温度反演,最佳测点组合的反演精度达到0.99以上,该研究为变压器油箱壁面监测点位的选取提供了可靠理论支撑。
The converter transformer is affected by harmonic excitation in actual operation
and its loss and temperature rise are significantly higher than those of the fundamental rated condition
which poses a serious challenge to the long-term operation stability of the equipment. Firstly
based on the actual structural parameters of the converter transformer
a three-dimensional simulation model is constructed to obtain the magnetic flux density distribution and loss characteristics of the transformer under fundamental and harmonic conditions. The thermal-flow coupling simulation model is built to reveal the distribution law of temperature field and flow field. The results show that the transformer loss and winding hot-spot temperature increase significantly after considering harmonics. Secondly
the loss suppression effect is studied by adding electrical shielding and magnetic shielding devices on the wall of the fuel tank
and the magnetic shielding suppression effect is more prominent. On this basis
the influences of the length
thickness and height of the shielding device on the loss of the fuel tank are analyzed. The response surface method combined with the satisfaction function is used to construct a multi-objective optimization model
and the parameters are globally optimized. After optimization
the total loss of the fuel tank wall and the winding hot-spot temperature are significantly reduced. Finally
based on the optimized transformer tank wall
the correlation between the measuring points in each region and the hot-spot temperature of the winding is calculated
and the GA-BP neural network model is introduced to invert the points with high correlation. The results show that the temperature inversion of different combinations of high correlation measuring points are carried out
and the inversion accuracy of the best combination of measuring points is more than 0.99. This study provides a reliable theoretical support for the selection of monitoring points on the wall of transformer tank.