1. 西安理工大学电气工程学院,西安,710048
2. 西安理工大学理学院,西安,710054
收稿:2026-06-30,
纸质出版:2026
移动端阅览
尹健宁, 曾晓宝, 徐鸣, 等. 基于振荡电路的可控Z源直流断路器的开断特性[J]. 高电压技术, 2026,52(6):2678-2688.
YIN Jianning, ZENG Xiaobao, XU Ming, et al. 基于振荡电路的可控Z源直流断路器的开断特性[J]. 2026, 52(6): 2678-2688.
尹健宁, 曾晓宝, 徐鸣, 等. 基于振荡电路的可控Z源直流断路器的开断特性[J]. 高电压技术, 2026,52(6):2678-2688. DOI: 10.13336/j.1003-6520.hve.20251008.
YIN Jianning, ZENG Xiaobao, XU Ming, et al. 基于振荡电路的可控Z源直流断路器的开断特性[J]. 2026, 52(6): 2678-2688. DOI: 10.13336/j.1003-6520.hve.20251008.
随着光伏发电系统装机容量的不断增长,直流侧电压逐渐升高,为断路器在高电压下进行全电流的快速开断提出了新的需求。为实现断路器快速且无电弧的开断,该文提出了一种基于振荡电路的可控Z源直流断路器(oscillation-circuit-based controllable Z-source DC circuit breaker,OCZ-DCCB)。在该拓扑结构中,通过控制晶闸管(silicon controlled rectifier,SCR)导通,使得系统正常运行状态下即可预充电支路中的电容C进行预充电,从而振荡支路中电容和电感产生振荡电流,从而实现对直流线路中全电流(10 A~10 kA)的快速开断。同时解决了传统Z源直流断路器出现故障电流上升率不足时导致晶闸管无法自关断进而无法开断小电流问题和瞬态误触发问题。该文提出的OCZ-DCCB与有源Z源直流断路器(active Z-source DC circuit breaker,AZ-DCCB)相比,在DC150 V时开断故障电流时间缩短了22倍。该文提出的OCZ-DCCB在DC1 500 V时,短路故障情况下,能量正向和反向流动时的开断时间分别为0.30 ms和0.25 ms,验证了所提方案的快速性和有效性。该结构通过与全控型器件绝缘栅双极型晶体管(insulated gate bipolar transistor,IGBT)结合,有效利用IGBT来满足直流微电网中复杂的能量流动需求,实现对电流的提前和有计划的切断。通过仿真对OCZ-DCCB进行了验证,结果表明其具有快速开断能力,并能适应不同的直流电网电压等级,证实了其有效性和适用性,为直流断路器在高电压下进行全电流的可靠开断提供了一种新的解决方案。
With the continuous growth of photovoltaic (PV) power generation capacity and the gradual increase in DC side voltage levels
new requirements have been imposed on circuit breakers to achieve rapid full-current interruption under high-voltage conditions. To realize fast and arc-free interruption
this paper proposes an oscillation-circuit-based controllable Z-source DC circuit breaker (OCZ-DCCB). In the proposed topology
by controlling the conduction of the silicon controlled rectifier (SCR)
the capacitor C in the pre-charging branch is charged during normal system operation. This facilitates the generation of an oscillating current via the capacitor and inductor in the oscillation branch
thereby achieving rapid interruption of the full load current (10 A to 10 kA) in the DC line. Furthermore
the proposed design effectively addresses the issues of thyristor self-commutation failure under insufficient fault current rise rates and transient false triggering
which are common limitations in traditional Z-source DC circuit breakers. Compared with the active Z- source DC circuit breaker (AZ-DCCB)
the OCZ-DCCB reduces the fault current interruption time by a factor of 22 at DC 150 V. Under a short-circuit fault condition at DC 1 500 V
the interruption time for forward and reverse energy flows is 0.30 ms and 0.25 ms
respectively
verifying the rapidity and effectiveness of the proposed scheme. By integrating with the fully controlled device insulated gate bipolar transistor (IGBT)
the structure effectively utilizes the IGBT to meet complex energy flow demands in DC microgrids
enabling proactive and scheduled current interruption. The OCZ-DCCB is verified by simulation
and the results demonstrate its rapid interruption capability and adaptability to various DC grid voltage levels. These findings confirm its effectiveness and applicability
providing a novel solution for reliable full-current interruption of DC circuit breakers under high-voltage conditions.
0
浏览量
2
下载量
0
CSCD
关联资源
相关文章
相关作者
相关机构
京公网安备11010802024621