Traditional research on modal resonance has primarily focused on renewable energy connected to grid systems in terrestrial applications. However
the offshore wind power VSC-HVDC system exhibits significant parameter differences between submarine cables and overhead transmission lines
necessitating clarification of the influence mechanism of submarine cable parameters on system modal resonance. We investigated the interaction between wind turbine grid-side converter (GSC) and VSC-HVDC converters
and examined the impact patterns of submarine cable capacitance and reactance on modal resonance. Moreover
we elucidated the resonant interaction between grid-following controlled GSC and grid-forming controlled VSC-HVDC converters
and establised analytical mapping relationships among submarine cable capacitance/inductance parameters
open-loop modes
and their residues. Critical discoveries indicate that submarine cable capacitance modifies system modal resonance through resonance intensity variation and open-loop mode displacement
thus the oscillation damping is in nonlinear characteristics in VSC-HVDC system
and submarine cable inductance amplifies resonance intensity via residue mechanisms;meanwhile
elevated parameters will intensify the resonance severity and degrade system damping. Time-domain simulations confirm theoretical predictions. Therefore
these distinct mechanisms
contrasting fundamentally with overhead transmission lines behaviors