The lightning impulse breakdown properties of multi-component mixed insulating oil under long oil gaps are crucial parameters for evaluating its insulation performance. These characteristics provide valuable guidance for optimizing transformer structure design and serve as a key foundation for ensuring the safe and reliable operation of high-voltage and large-capacity transformers. This study investigates the lightning impulse discharge characteristics of long oil gaps in multi-component mixed insulating oil
focusing on the discharge point development speed
streamer development morphology
breakdown voltage
and Weibull distribution under oil gap lengths ranging from 25 mm to 105 mm. The findings reveal that
due to the acceleration effect of ester insulating oil flow within the multi-component mixture
the development speed of lightning impulse discharge under long oil gaps is significantly faster than that of mineral oil. Under short-gap conditions
the discharge point development speed of multi-component mixed insulating oil is also higher for both positive and negative electrodes compared to mineral oil. The streamer morphologies under positive and negative polarities exhibit multi-branched filaments and single filaments
respectively. For long-gap conditions
the streamer morphologies are bush-like for positive polarity and tree-like for negative polarity. In terms of breakdown voltage
the positive polarity lightning impulse breakdown voltage of multi-component mixed insulating oil is slightly lower than that of mineral oil but significantly higher than that of ester insulating oil. Furthermore
it is comparable to binary and ternary mixed insulating oils. The negative polarity lightning impulse breakdown voltage of multi-component mixed insulating oil is 16%~50% higher than that of existing mixed insulating oils. Specifically
it aligns closely with mineral oil at gaps between 85 mm and 105 mm.