1. 武汉大学电气与自动化学院,武汉,430072
2. 武汉大学新型电力系统与国际标准研究院,武汉,430072
3. 中国南方电网有限责任公司超高压输电公司电力科研院,广州,510663
收稿:2026-04-30,
纸质出版:2026
移动端阅览
毕吉禹, 黄道春, 周硕伦, 等. 生长态树冠火条件下导线-板长空气间隙直流击穿特性[J]. 高电压技术, 2026,52(4):1848-1857.
BI Jiyu, HUANG Daochun, ZHOU Shuolun, et al. 生长态树冠火条件下导线-板长空气间隙直流击穿特性[J]. 2026, 52(4): 1848-1857.
毕吉禹, 黄道春, 周硕伦, 等. 生长态树冠火条件下导线-板长空气间隙直流击穿特性[J]. 高电压技术, 2026,52(4):1848-1857. DOI: 10.13336/j.1003-6520.hve.20250303.
BI Jiyu, HUANG Daochun, ZHOU Shuolun, et al. 生长态树冠火条件下导线-板长空气间隙直流击穿特性[J]. 2026, 52(4): 1848-1857. DOI: 10.13336/j.1003-6520.hve.20250303.
为给山火条件下直流架空输电线路空气间隙击穿风险差异化防控提供支撑,搭建了不同火焰类型下导线-板电极长空气间隙击穿特性试验平台,对比树种、火焰类型、间隙距离对间隙直流击穿特性影响。结果表明:生长态树冠火可导致空气间隙绝缘强度明显下降,最大火势阶段,5 m间隙下松树树冠火与柏树树冠火平均击穿电压梯度分别为84.7 kV/m与43.2 kV/m,分别为同海拔纯空气间隙平均击穿电压梯度的31.6%与16.1%,树种差异对击穿特性影响主要表现在火焰区燃烧参数与非火焰区燃烧颗粒尺寸;间隙长度不同,树冠火火焰桥接平均比例若接近,平均击穿电压梯度也接近;9 m间隙下木垛火火焰桥接比例低于5 m间隙,前者间隙绝缘强度也低于后者,原因在于9 m间隙下非火焰段温升与烟雾颗粒浓度皆高于5 m间隙;生长态树冠火对间隙绝缘强度的影响较木垛火大,火焰类型差异对击穿特性的影响由烟雾区主导,间隙长度增加,树冠火和木垛火条件下空气间隙直流击穿特性差异减小。
In order to provide support for the differentiated prevention and control of air gap breakdown risks in DC overhead transmission lines under wildfire conditions
this paper establishes a conductor-plane long air gap breakdown test platform for transmission lines under crown fire and crib fire conditions
and compares the effects of tree species
fire types
gap distance and other factors on the DC breakdown characteristics of conductor-plane air gap. The results show that the living state crown fire leads to a significant decrease in the insulation strength of the air gap. At the maximum burning phase
the average breakdown voltage gradient of pine crown fire and cypress crown fire at a 5 m air gap are 84.7 kV/m and 43.2 kV/m
respectively
which is 31.6% and 16.1% of the average breakdown voltage gradient of a pure air gap at the same altitude. The influence of tree species difference on the breakdown characteristics is mainly reflected in the combustion parameters in the flame zone and the combustion particle size in the non-flame zone. Regardless of gap length
the average proportion of crown fire flame bridging is close
and the average breakdown voltage gradient is also close. However
for wood crib fires
the flame bridging proportion under a 9 m gap is lower than that under a 5 m gap
while the insulation strength of the former is also lower. The reason is that the temperature rise and smoke particle concentration of non-flame section under the 9 m gap are higher than those of the 5 m gap. The influence of the living state crown fire on gap insulation strength is greater than that of crib fire. The influence of fire type difference on breakdown characteristics is mainly dominated by smoke zone. With the increase of the length of air gap
the difference of air gap DC breakdown characteristics between crown fire and crib fire decreases.