1. 河北省分布式储能与微网重点实验室(华北电力大学),保定,071003
2. 国网冀北电力有限公司,北京,100054
纸质出版:2025
移动端阅览
高本锋, 陈宗良, 于思奇, 等. 基于等效阻抗的虚拟同步机短路电流解析计算方法及影响因素分析[J]. 高电压技术, 2025,51(12):6022-6032.
高本锋, 陈宗良, 于思奇, et al. 基于等效阻抗的虚拟同步机短路电流解析计算方法及影响因素分析[J]. 2025, 51(12): 6022-6032.
高本锋, 陈宗良, 于思奇, 等. 基于等效阻抗的虚拟同步机短路电流解析计算方法及影响因素分析[J]. 高电压技术, 2025,51(12):6022-6032. DOI: 10.13336/j.1003-6520.hve.20250123.
高本锋, 陈宗良, 于思奇, et al. 基于等效阻抗的虚拟同步机短路电流解析计算方法及影响因素分析[J]. 2025, 51(12): 6022-6032. DOI: 10.13336/j.1003-6520.hve.20250123.
构网型控制技术因其主动支撑特性在新型电力系统中应用愈加广泛,电网短路故障时构网型逆变器易出现过流现象,通常采用虚拟导纳以限制短路电流,而虚拟导纳应如何在故障电流解析计算中进行等值的问题亟待解决。为此,该文针对采用虚拟导纳限流的虚拟同步机(virtual synchronous generator
VSG)并网系统,提出电网三相对称短路故障下基于等效阻抗的VSG短路电流计算方法。首先,根据传统短路电流计算给出基于等效阻抗的短路电流计算表达式;其次,在电流内环趋稳时间尺度下求解等效阻抗并建立VSG逆变电源故障等值模型,推导得出考虑虚拟内电势变化的短路电流解析表达式;然后,基于此表达式分析了不同控制参数与故障程度下对VSG短路电流的影响;最后,通过MATLAB/simulink仿真平台验证了所提出的基于等效阻抗的VSG短路电流计算方法以及影响因素分析的正确性。
Grid-forming control technology
due to its active support capabilities
is increasingly applied in modern power systems. However
grid-forming inverters are prone to overcurrent phenomena during grid short-circuit faults. To address this issue
virtual admittance is commonly employed to limit short-circuit currents
yet the equivalent modeling of virtual admittance in fault current analytical calculations remains a critical challenge. This paper proposes an equivalent impedance-based short-circuit current calculation method for virtual synchronous generator (VSG) grid-connected systems utilizing virtual admittance current limiting
under three-phase symmetrical short-circuit fault scenarios. First
based on traditional short-circuit current calculation principles
the expression for short-circuit current calculation using equivalent impedance is derived. Second
the equivalent impedance is solved under the current inner-loop stabilization time scale
and a fault equivalent model for VSG inverter power sources is established
and an analytical expression for short-circuit current that takes account of variations in virtual internal potential is deduced. Subsequently
the influence of different control parameters and fault severity levels on the VSG short-circuit current is analyzed by using the derived expression. Finally
the correctness of the proposed equivalent impedance-based VSG short-circuit current calculation method and the related influencing factors analysis is validated through simulations on the MATLAB/Simulink platform.
0
浏览量
0
下载量
0
CSCD
关联资源
相关文章
相关作者
相关机构
京公网安备11010802024621