光纤复合架空地线(optical fiber composite overhead ground wire,OPGW)易遭受雷击而引起烧蚀损伤,烧蚀电弧涉及复杂非线性电磁热的等离子体放电过程。该文充分考虑雷电动态电弧发展过程中电磁热流体间的强弱耦合关系,建立了配网OPGW雷击过程的动态烧蚀模型,并开展配网OPGW雷击烧蚀损伤模拟试验,对比分析转移电荷量、OPGW截面和雷电流幅值对OPGW雷击损伤的影响规律。开展OPGW雷击损伤模拟放电试验,分析转移电荷量对3种型号配电线路OPGW的烧蚀损伤过程。仿真与试验结果表明,转移电荷量由50 C增大到150 C时,仿真与试验的烧蚀深度分别增大了5.34倍和4.38倍,烧蚀面积分别增大了11.5倍和4.71倍,由于试验中电弧扫掠位置不固定,因此烧蚀面积增大程度并不明显;OPGW单股截面小的受损伤影响较大,在具有拉力条件下的试验中单股截面小的更容易发生断股现象,但其整体性能受影响较小;雷电电弧高温持续烧蚀是OPGW雷击损伤的主要原因,当雷电流C分量的幅值从设定值的97.5%减小至90%时,烧蚀深度减小了10.49%,烧蚀面积减小了14.37%。因此,应根据当地雷电灾害情况与施工条件选择合适的OPGW型号。
Optical fiber composite overhead ground wire(OPGW) is susceptible to lightning strikes which induce ablation damage. The ablation arc corresponds to a complex nonlinear electromagnetic-thermal plasma discharge process. In this study
the strong and weak coupling effects of electromagnetic
thermal and fluid fields during the evolution of dynamic lightning arcs are fully considered
and a dynamic ablation model for the lightning strike process of OPGW in distribution networks is established. Simulations are conducted to investigate lightning-induced ablation damages to distribution-network OPGW
and the influences of transferred charge quantity
OPGW cross-sectional structure
and lightning current amplitude on OPGW lightning damage are comparatively analyzed. Discharge simulation tests on lightning damage of OPGW were carried out to analyze the effect of transferred charge on the ablation damage process of three types of OPGW for distribution lines. Simulation and experimental results indicate that
when the transferred charge rises from 50 C to 150 C
the ablation depth increases by 5.34 times in simulation and 4.38 times in experiment
while the ablation area increases by 11.5 times and 4.71 times
respectively. Single strands with smaller cross-sections in OPGW are more vulnerable to lightning damage and prone to fracture under tensile load
whereas the overall structural performance of OPGW remains relatively stable. High-temperature continuous ablation caused by lightning arcs is the primary cause of OPGW lightning damage. When the amplitude of lightning current C-component drops from 97.5% to 90%
the ablation depth is reduced by 10.49% and the ablation area decreases by 14.37%. Consequently
optimal OPGW types should be selected according to local lightning property and actual engineering construction conditions.