ZHAO Yingjie, ZHANG Yao, LI Yongfei, et al. 考虑架空线路动态热定值和N‒1安全准则的源-网-储系统分布鲁棒优化运行方法[J]. 2025, 51(9): 4819-4832.DOI: 10.13336/j.1003-6520.hve.20241201.
考虑架空线路动态热定值和N‒1安全准则的源-网-储系统分布鲁棒优化运行方法
摘要
新能源随机性使得电力系统潮流复杂多变,加之大量新能源需要远距离输送消纳,输电阻塞问题日益严重。动态热定值(dynamic line rating,DTR)技术能够提升既有架空线路的输电能力,充分发挥系统的灵活调节能力。特别是在N‒1事故场景下,采用DTR技术提升线路输送能力,能够缓解严重输电阻塞。然而,传统方法在考虑N‒1事故时存在维数灾难问题,因此应用DTR技术仍然存在挑战性。为此,提出了一种两阶段分布鲁棒优化(distributionally robust optimization,DRO)方法以提升架空线路的输电能力。首先,构建了架空线路暂态温度计算模型并做适当简化处理,从而保证后续优化模型的凸性。随后,建立了考虑DTR和N‒1安全准则的两阶段DRO模型以避免N‒1事故下的持续停电,考虑无功与网损的线性化交流潮流模型能够更准确地计算线路潮流。最后,使用IEEE-24节点系统和IEEE-118节点系统验证了所提方法的有效性。
Abstract
Due to the randomness of renewable energy
power flow becomes complex and variable. In addition
a large amount of renewable energy has to be remotely transferred and consumed. Therefore
transmission congestion becomes increasingly serious. Dynamic line rating (DTR) technology can improve the transmission capacity of existing overhead lines and fully utilize the flexibility of power system. Especially under N‒1 contingency
applying DTR technology can alleviate severe transmission congestion. However
it is still challenging to optimize DTR with security assurance
which suffers from dimension curse in traditional approaches under N‒1 contingency. In this paper
a two-stage distributionally robust optimization (DRO) approach is proposed to improve the transmission capacity of overhead lines. A transient temperature calculation model of overhead lines is firstly proposed and simplified to preserve the convexity property in the following DRO model. Then
a two-stage DRO model for source-grid-storage system considering DTR of overhead lines and N‒1 security criterion is established to avoid the blackout under N‒1 contingency. A linearized alternative current power flow model considering reactive power and network losses is utilized to calculate the line current more accurately. Finally
case studies on IEEE-24 bus system and IEEE-118 bus system verify the effectiveness of the proposed method.