叶昊亮, 杨勇, 曹俊平, 等. 不同接地方式下的电缆序阻抗参数计算与分析[J]. 高电压技术, 2025,51(10):5186-5197.
YE Haoliang, YANG Yong, CAO Junping, et al. 不同接地方式下的电缆序阻抗参数计算与分析[J]. 2025, 51(10): 5186-5197.
叶昊亮, 杨勇, 曹俊平, 等. 不同接地方式下的电缆序阻抗参数计算与分析[J]. 高电压技术, 2025,51(10):5186-5197. DOI: 10.13336/j.1003-6520.hve.20240665.
YE Haoliang, YANG Yong, CAO Junping, et al. 不同接地方式下的电缆序阻抗参数计算与分析[J]. 2025, 51(10): 5186-5197. DOI: 10.13336/j.1003-6520.hve.20240665.
电缆序阻抗参数与继电保护整定计算直接相关。电缆的序阻抗参数受其敷设方式影响,正零序参数与护套、保护器、回流缆的接地方式息息相关。为此以经典卡松回路方程(Carson)为基础,提出了一种适用于不同接地方式下的多回电缆正零序参数计算方法。对电缆串联阻抗矩阵与序阻抗计算,结合电磁暂态软件PSCAD/EMTDC建模仿真,验证了算法的正确性与精确性。最后对电缆序阻抗参数的影响因素进行研究,结果表明:护套双端接地时正序电抗明显减小、接地方式不同导致零序参数差异显著,护套单端接地时零序参数显著增大,敷设回流缆可适当减小零序参数;当电缆“品”字排列时,回流缆敷设距离线芯距离与正序电阻呈负相关,与零序阻抗呈正相关;土壤电阻率变化不影响电缆正序参数,仅对护套单端接地与回流缆加保护器接地方式下的零序参数产生影响;当两回电缆并联时,护套单端接地方式下零序参数显著增大、护套双端接地与交叉互联接地方式下零序参数基本不变、回流缆加保护器接地方式下零序阻抗增大程度与回流缆敷设位置相关。
The correctness of the cable sequence impedance parameters is directly related to the relay protection setting calculation. The sequence impedance parameter of the cable is affected by its laying method
and the positive zero sequence parameter is closely related to the grounding method of the sheath
protector
and return cable. Based on the classic Carson loop equation (Carson)
this paper proposes a method for calculating the positive zero sequence parameters of multi-circuit cables suitable for different grounding methods. The full-dimensional impedance matrix and sequence impedance calculation of the cable
combined with the electromagnetic transient software PSCAD/EMTDC modeling and simulation
verified the correctness and accuracy of the algorithm. Finally
the influencing factors of the cable sequence impedance parameters were studied. The results show that the positive sequence reactance is significantly reduced when the sheath is grounded at both ends. Different grounding methods result in significant differences in the zero sequence parameters. When the sheath is grounded at one end
the zero sequence parameters are significant. As the value increases
laying the return cable can appropriately reduce the zero-sequence parameter; when the cables are arranged in pin-shape
the distance between the return cable laying and the core is negatively correlated with the positive sequence resistance and positively correlated with the zero-sequence impedance; the change in soil resistivity does not affect the positive sequence parameters of the cable but only affects the zero sequence parameters under the single-end grounding of the sheath and the grounding of the return cable plus protector; when the two cables are connected in parallel
the zero-sequence parameters increase significantly under the single-end grounding of the sheath
and the zero-sequence parameters are basically unchanged under the double-end grounding of the sheath and the cross-connection grounding method. The degree of increase in the zero-sequence impedance under the return cable plus protector grounding method is related to the laying position of the return cable.