1. 合肥工业大学电气与自动化工程学院,合肥,230009
2. 国网安徽省电力有限公司亳州供电公司,亳州,236800
收稿:2025-09-30,
纸质出版:2025
移动端阅览
董冰冰, 安晋阳, 金林林. 恒定低工作系数下气体间隙开关触发放电特性[J]. 高电压技术, 2025,51(9):4620-4628.
DONG Bingbing, AN Jinyang, JIN Linlin. 恒定低工作系数下气体间隙开关触发放电特性[J]. 2025, 51(9): 4620-4628.
董冰冰, 安晋阳, 金林林. 恒定低工作系数下气体间隙开关触发放电特性[J]. 高电压技术, 2025,51(9):4620-4628. DOI: 10.13336/j.1003-6520.hve.20232348.
DONG Bingbing, AN Jinyang, JIN Linlin. 恒定低工作系数下气体间隙开关触发放电特性[J]. 2025, 51(9): 4620-4628. DOI: 10.13336/j.1003-6520.hve.20232348.
气体间隙开关用于配电网快速旁路操作结构简单、成本低,但其操作过程中的工作系数因触发条件参数确定而难以快速调整,目前恒定低工作系数下触发条件参数对气体开关触发特性影响的研究相对较少。为此搭建了恒定低工作系数下气体开关喷射等离子体触发特性研究平台。结果表明,在恒定低工作系数下,改变气体介质组分含量,气体间隙开关喷射等离子体演化形态与其特征参数(轴向高度、径向直径)存在明显差异,触通时延未发生显著变化。气压增大阻碍了等离子体喷射发展,引起喷射等离子体轴向高度减小,导致气体开关触通时延增加,临界工作系数随之增大;与N2以及混合气体(N2和SF6)相比,SF6中等离子体喷射轴向高度随气压增大而衰减的幅度较大,且开关触通时延和临界工作系数增大明显。改变主间隙距离,气体开关主间隙诱导击穿过程存在差异,其触通时延和等离子体喷射特征量的变化较为显著,且临界工作系数随间距增大而提高。提高触发电压,触发腔电弧通道电功率增大,弧道能量沉积效率降低,等离子体喷射高度增大,气体开关触通能力提升,其临界工作系数和触通时延均明显降低。研究结果可为气体间隙开关性能优化与工程应用提供理论指导。
The gas gap switch used in the fast bypass operation of the distribution network has obvious advantages
simple structure and low cost; however
the working coefficient in the operation process is difficult to adjust quickly due to the determination of the trigger condition parameters. At present
there is a lack of research on the influence of the trigger condition parameters on the trigger performance of the gas switch under constant low working coefficient. This paper builds a research platform for the triggering characteristics of gas switch jet plasma under a constant low working coefficient. The results show that
under the constant low working coefficient
when changing the content of the gas medium component
there is a significant difference between the evolution morphology of the gas gap switch jet plasma and its characteristic parameters (axial height
radial diameter)
and the contact delay does not change significantly. The increase of the pressure hinders the development of the plasma jet
which causes the axial height of the jet plasma to decrease
resulting in the increase of the contact time delay of the gas switch and the increase of the critical working coefficient. Compared with N2 and mixed gas of N2 and SF6
the axial height of plasma jet in SF6 decreases greatly with the increase of gas pressure
and the increase of switching delay and critical working coefficient is obvious. When the main gap distance is changed
the main gap induced breakdown process of the gas switch is different
and the change of the switching time delay and the plasma ejection characteristic quantity is more significant; meanwhile
the critical working coefficient increases with the increase of the distance. With the increase of the trigger voltage
the electric power of the arc channel of the trigger chamber increases
the energy deposition efficiency of the arc channel decreases
the plasma jet height increases
the contact capacity of the gas switch increases
and the critical working coefficient and the contact delay are significantly reduced. The research results can provide theoretical guidance for the performance optimization and engineering application of gas gap switches.