XU Jiajun, KAN Jiarong, WU Yunya, et al. Reconfigurable Off-grid Equalization Control Strategy for Modular Multilevel Converter Based Battery Energy Storage System[J]. 2025, 49(12): 4947-4956.
XU Jiajun, KAN Jiarong, WU Yunya, et al. Reconfigurable Off-grid Equalization Control Strategy for Modular Multilevel Converter Based Battery Energy Storage System[J]. 2025, 49(12): 4947-4956. DOI: 10.13335/j.1000-3673.pst.2025.0597.
模块化多电平电池储能系统(modular multilevel converter based battery energy storage system,MMC-BESS)可以平抑新能源出力波动,有助于提升新能源消纳能力。针对MMC-BESS并网均衡受限的问题,该文提出了一种可重构离网分层均衡控制策略。顶层针对相间电压差异,通过改变相间均衡权重系数,动态调整放电均衡时长。底层针对相内电压差异,引入模块级电压排序算法,动态选择跨相均衡目标。通过双层均衡控制策略,实现储能单元的相间与相内电压均衡,提高储能系统的能量利用率。加入主动限流控制,避免均衡电流过大,保障离网均衡运行安全。在Matlab/ Simulink中搭建仿真模型,仿真结果和实验平台的实验结果表明,所提控制策略可有效实现MMC-BESS的相间与相内电压均衡。
Abstract
The modular multilevel converter based battery energy storage system (MMC-BESS) can effectively mitigate fluctuations in renewable energy generation output
enhancing renewable energy accommodation capacity. This paper proposed a reconfigurable off-grid hierarchical equalization control strategy to address the grid-connected equalization constraints in MMC-BESS. For inter-phase voltage imbalance in the top layer control
the discharge equalization duration was dynamically adjusted by modifying inter-phase equalization weighting coefficients. In the bottom layer control targeting intra-phase voltage differences
a module-level voltage sorting algorithm was introduced to dynamically select cross-phase equalization targets. Through this dual-layer equalization control strategy
voltage equalization among the energy storage units was achieved at both the inter-phase and intra-phase levels
thereby improving the energy utilization rate of the storage system. Active current limiting was incorporated to prevent excessive equalization current
ensuring the safety of off-grid equalization operation. A simulation model was established in Matlab/Simulink
and both simulation results and experimental platform tests demonstrate that the proposed control strategy effectively achieves inter-phase and intra-phase voltage equalization in MMC-BESS.