LI Haifeng, 1, LIN Lidong, et al. A Novel Phase-locked Loop for Photovoltaic Grid-connected Systems in High-proportion Renewable Energy Scenarios[J]. 2025, 49(10): 4330-4341.
LI Haifeng, 1, LIN Lidong, et al. A Novel Phase-locked Loop for Photovoltaic Grid-connected Systems in High-proportion Renewable Energy Scenarios[J]. 2025, 49(10): 4330-4341. DOI: 10.13335/j.1000-3673.pst.2024.2251.
电网同步锁相是光伏跟网型并网系统稳定可靠运行的关键技术之一。高比例新能源场景下,电网面临着电压扰动、电压不平衡、谐波畸变及直流偏置等诸多问题。为此,提出一种基于同步参考坐标系锁相环和环前型滑动平均滤波结构(pre-loop moving average filter,PMAF)的新型锁相环。该锁相环采用相位补偿方法校正频率偏移时的锁相误差。同时,考虑PMAF的相频耦合特性,设计了一种角频率补偿方法以提高锁相环的动态性能,建立其小信号模型并进行稳定性分析。接着设计了一种故障检测模块,实现两种补偿支路的投入和切除以适应不同工况。仿真验证了该新型锁相环在相位跳变、频率偏移、电压畸变等复杂电网条件下的有效性。最后,在高比例新能源电网中进行了新型锁相环的暂态性能测试。结果表明该锁相环能快速锁定电网电压相位,避免电压电流的振荡发散,有利于系统在故障后快速平稳地恢复。
Abstract
Grid synchronization is one of the key technologies for the stable and reliable operation of grid-connected photovoltaic systems. In high-proportion renewable energy
the power grid faces problems such as voltage disturbance
voltage imbalance
harmonic distortion
DC offset
and so on. To this end
a new phase-locked loop based on a synchronous reference frame phase-locked loop and a pre-loop moving average filter is proposed. It employs a phase compensation method to correct the phase-locked error when there is a frequency deviation. At the same time
considering the phase-frequency coupling characteristics of PMAF
an angular frequency compensation method is designed to improve the dynamic performance of the phase-locked loop. A small signal model is established
and a stability analysis is conducted. Following that
a fault detection module is designed to realize the input and removal of the two compensation branches to adapt to different working conditions. Simulations verify the effectiveness of this new phase-locked loop under complex grid conditions such as phase jump
frequency deviation and voltage distortion. Finally
the transient performance test of the new phase-locked loop is carried out in the high-proportion renewable energy generation model. The results indicate that the phase-locked loop can lock the grid voltage phase as quickly as possible
avoid the oscillation and divergence of voltage and current
and is conducive to the rapid and stable recovery of the system after a fault.