LI Zainan, ZHU Xinchen, ZHOU Niancheng, et al. Research on Hybrid Current Limiting Method of Half-bridge MMC DC Faults[J]. 2026, 46(11): 4682-4692.DOI: 10.13334/j.0258-8013.pcsee.251479.
半桥型模块化多电平高压直流输电(modular multilevel converter based high voltage direct current,MMC-HVDC)系统的直流线路短路故障后,仅通过挖掘MMC换流站的限流潜力难以平衡直流限流和桥臂过流矛盾。针对该问题,提出一种混合型限流方法,在故障后依次投入减少子模块数目的控制限流和串联桥臂阻尼模块的设备限流,以平衡直流限流和桥臂过流矛盾;理论分析控制限流机理,指出在极端工况下,不同限流程度的控制限流均无法避免与强交流相连的桥臂绝缘栅双极型晶体管(insulated gate bipolar translator,IGBT)闭锁;从桥臂过流约束推导控制限流的参数边界,给出设备限流配合的启动时刻,根据桥臂电流变化自适应串联不同数目的桥臂阻尼模块,以较小成本达到较好限流效果。测试结果表明,相比其他混合型限流方法,所提的限流方法最高可将桥臂电流峰值降低30.71%,其峰值电流低于IGBT安全边界。
Abstract
After a short-circuit fault in a half-bridge MMC-HVDC DC line
it is difficult to balance the contradiction between DC limiting and bridge arm over-current only by exploiting the current limiting potential of the MMC. To address this problem
this paper proposes a hybrid fault current limiting (FCL) method to balance the DC current limiting and the bridge arm over-current by sequentially putting in control current limiting (CCL) with a reduced number of sub-modules and series adaptive series bridge arm damping module-based device current limiting (DCL) after a fault. The mechanism of CCL is analyzed theoretically
and it is noted that insulated gate bipolar translator (IGBT) blocking cannot be avoided
particularly when connected to a strong AC system
due to different FCL effects in the CCL under extreme fault conditions. From the constraints of bridge arm overcurrent
the parameter boundaries of the CCL are deduced
and the starting moments of the DCL are given. Adaptive series connection of different numbers of bridge arm damping modules according to the change of bridge arm current achieves a better current limiting effect at the minimum cost. The test results show that compared with other hybrid FCL methods
the proposed current limiting method can reduce the peak bridge arm current by up to 30.71%
with the peak current lower than the IGBT safety boundary.