LI Meng, DU Xiaotong, HE Jinghan, et al. Adaptive Impedance-based Pilot Protection for Distribution Lines With T-connected Inverter Based Resources[J]. 2026, 46(11): 4377-4388.
LI Meng, DU Xiaotong, HE Jinghan, et al. Adaptive Impedance-based Pilot Protection for Distribution Lines With T-connected Inverter Based Resources[J]. 2026, 46(11): 4377-4388.DOI: 10.13334/j.0258-8013.pcsee.250714.
在含T接逆变电源(inverter based resources,IBRs)配电系统场景下,跟网型与构网型IBR的控制策略差异导致故障电流呈现多源耦合非线性特性,现有保护面临误动/拒动风险。该文提出基于等效IBR序阻抗相角区间的自适应纵联阻抗方法。首先,依据IBR故障穿越控制策略,量化并网点电压与跟网型和构网型IBR正序输出电流的相角差区间,分析负序网络下IBR的等值阻抗形式,统一等效不同类型IBR在序网络下的阻抗相角区间,实现故障特征与源端控制解耦;继而,构建基于T接点估计电压与差动电流相角差的自适应正序阻抗保护判据,并针对不对称高阻故障提出负序阻抗相角累加和乘积极性的附加保护判据,提升保护速动性及抗过渡电阻能力。结果表明,所提保护方案最快可在8 ms内识别故障,耐受500 Ω高阻故障,无需采样数据同步,且不受IBR类型和容量影响。
Abstract
In distribution systems with T-connected inverter-based resources (IBRs)
differences in control strategies between grid-following and grid-forming IBRs lead to multi-source coupled nonlinear fault current characteristics
potentially causing maloperation or failure of conventional protection schemes. An adaptive pilot impedance protection method
based on equivalent IBR sequence impedance phase angle intervals
is proposed. The phase angle difference intervals between the point of common coupling voltage and positive-sequence output currents of both types of IBRs are quantified according to their fault ride-through control strategies. Impedance characteristics of IBRs in the negative-sequence network are analyzed
and equivalent sequence impedance phase angle intervals for different IBRs are unified in sequence networks to decouple fault characteristics from source-side control dynamics. Consequently
an adaptive positive-sequence impedance protection criterion is constructed based on the phase angle difference between the estimated T-node voltage and differential current. For asymmetric high-resistance faults
this paper proposes an additional protection criterion
which combines the accumulation and polarity product of negative-sequence impedance phase angles
to enhance resistance to transition resistance. Simulation results show that the proposed protection scheme can identify faults within 8 ms
withstand 500 Ω high-resistance faults eliminate the need for sampling data synchronization
and remain unaffected by the type and capacity of IBR.