合环转供电是提高供电可靠性的关键手段,但直接合环可能产生较大冲击电流影响电网运行安全性。采用旋转潮流控制器(rotary power flow controller,RPFC)的方式能够实现台区的零感知合环,但电压调节轨迹不当将会带来RPFC接入点的电压越限问题。对此,提出一种基于两阶段最优路径的RPFC配电网柔性合环方法。首先,对输出电压运行轨迹进行合理规划,将其分为两阶段:第1阶段要求合环点两端电压相位一致并约束电压幅值相等,实现端电压的平稳过渡;第2阶段在相位一致的基础上,控制RPFC输出电压至目标值,使合环点两端电压幅值一致。然后,采用分相量夹角计算和旋转角协调控制,选择就近的旋转角设定值作为目标值,从而实现合环点两端电压无差调节;最后,仿真和实验对比分析所提方法将电压越限至少降低至30%,展示RPFC在实现配电网柔性合环中的重要应用价值。
Abstract
Non-stop power transfer is the key method to improve the reliability of power supply
but direct loop closing may produce excessive current and affect the safety of operation. Rotary power flow controller (RPFC) can realize zero-sensing loop of substations
but improper voltage regulation trajectory will cause voltage limit violations at the RPFC terminal. To address the issue
this paper proposes a flexible loop-closing method for distribution networks based on a two-stage optimal path using the RPFC. Firstly
the output voltage trajectory is systematically planned and divided into two stages: in the first stage
the voltage phases at both ends of the loop-closing point are aligned
and the voltage amplitudes are constrained to be equal
ensuring a smooth voltage transition. In the second stage
based on phase alignment
the RPFC output voltage is controlled to reach the target value
ensuring equal voltage amplitudes at both ends of the loop-closing point. Next
phase angle difference calculation and rotational angle coordination control are employed to select the nearest rotational angle setpoint as the target value
achieving precise voltage regulation at both ends of the loop-closing point. Finally
simulation and experimental comparative analyses demonstrate that the proposed method reduces voltage limit violations by at least 30%
showcasing the significant application value of the RPFC in achieving flexible loop closing in distribution networks.