Coupling Characteristics Analysis between Transient Rotor Angle Instability and Transient Over-voltage in Combined Generating System of Thermal Power and New Energy
YANG Yuxin, WANG Jinsong, ZHU Yongli, et al. Coupling Characteristics Analysis between Transient Rotor Angle Instability and Transient Over-voltage in Combined Generating System of Thermal Power and New Energy[J]. 2026, 46(8): 3080-3090.
YANG Yuxin, WANG Jinsong, ZHU Yongli, et al. Coupling Characteristics Analysis between Transient Rotor Angle Instability and Transient Over-voltage in Combined Generating System of Thermal Power and New Energy[J]. 2026, 46(8): 3080-3090.DOI: 10.13334/j.0258-8013.pcsee.242468.
In a thermal power-renewable energy combined transmission system
the transient power rotor angle instability of thermal power units and the transient over-voltage at the renewable energy generator terminals are important issues that limit the transmission capacity. First
an analytical equation for the power rotor angle variation of thermal power units considering the negative impedance characteristics of new energy is established
and the new transient power rotor angle stability characteristics of thermal power units after the integration of new energy are analyzed. Secondly
based on the Thévenin equivalent and vector analysis method
the transient over-voltage at the new energy machine terminal is analyzed
and the influencing factors of transient over-voltage are discussed. Next
through formula analysis and electromagnetic transient simulations
the coupling relationship between two types of transient over-voltages is highlighted. Finally
using a practical engineering case as an example
this study analyzes the dominant risk modes under different scenarios
and proposes operational modes under two integrated risk constraints. The research results provide technical references for the safe and stable operation of thermal power-renewable energy combined energy bases in the new situation.