Modeling and Resonance Mechanism Analysis of MMC-HVDC Under Unload Condition Considering the High Frequency Characteristics of Electromagnetic Current Transformer Measurement Link
HU Yinghong, SHEN Yuchen, YIN Guangzu, et al. Modeling and Resonance Mechanism Analysis of MMC-HVDC Under Unload Condition Considering the High Frequency Characteristics of Electromagnetic Current Transformer Measurement Link[J]. 2025, 45(18): 7136-7148.
HU Yinghong, SHEN Yuchen, YIN Guangzu, et al. Modeling and Resonance Mechanism Analysis of MMC-HVDC Under Unload Condition Considering the High Frequency Characteristics of Electromagnetic Current Transformer Measurement Link[J]. 2025, 45(18): 7136-7148. DOI: 10.13334/j.0258-8013.pcsee.240536.
During the operation of Zhangbei Renewable Energy flexible DC power grid demonstration project
high frequency resonance occurred many times in Kangbanuoer Island converter station under no-load condition. To solve this problem
we firstly consider the dynamic characteristics of electromagnetic current transformer measurement loop in modeling
obtain π-type equivalent circuit for the current measurement link of the cable
and build a mathematical model of flexible HVDC island absorbing new energy system with current measurement link under no-load condition. Secondly
the stability of the above mathematical model is analyzed
and the mechanism of high frequency resonance in the converter station under no-load condition is proposed. Then we conduct simulation and field test
which demonstrate the accuracy of the new energy system model and the rationality of the high frequency resonance mechanism of the island converter station caused by the measurement link of the current transformer. At the same time
the suppression measures of high frequency resonance are proposed
which are verified by simulation and field test. The research can provide important technical guidance for MMC-HVDC projects