Weimin YAO, Ruihua ZHANG, Youliang CHEN, et al. Mechanical Draft Wet Cooling Tower Performance Research Based on Enthalpy Difference Method Under Variable Operating Conditions[J]. Power Generation Technology, 2019, 40(5): 493-498.
Based on the enthalpy difference theory and the characteristics of the mechanical draft cooling tower
a mathematical method of the cooling tower performance was derived to analyze the influence of operating parameters on tower outlet water temperature. The results show that the influence of atmospheric pressure and dry-bulb temperature on the tower outlet water temperature is negligible. The wet-bulb temperature is the main environmental factor affecting the cooling tower performance. Cooling water flowrate
condenser heat load
failure cooling area and ventilation resistance all have a positive correlation with tower outlet water temperature. While the air flowrate of the fan increases
the tower outlet water temperature will decrease. The above conclusions will help to accurately predict the changing trend of tower outlet water temperature under variable operating conditions
and provide guidance for the adjustment of cooling tower operation under variable conditions.
Al-Waked R, Behnia M.Enhancing performance of wet cooling towers[J].Energy Conversion and Management, 2007, 48(10):2638-2648.
Gao M, Sun F Z, Wang K, et al.Experimental research of heat transfer performance on natural draft counter flow wet cooling tower under cross-wind conditi-ons[J].International Journal of Thermal Sciences, 2008, 47(7):935-941.
Chen Youliang, Sun Fengzhong, Wang Hongguo, et al.Experimental research of the cross walls effect on the thermal performance of wet cooling towers under crosswind conditions[J].Applied Thermal Engineering, 2011, 31(17/18):4007-4013.