黄学民, 邓俊文, 邓京, 等. 交流滤波器避雷器电气特性分析中不同仿真模型的影响[J]. 中国电力, 2021,54(7):141-148.
Xuemin HUANG, Junwen DENG, Jing DENG, et al. Influence of Different Simulation Models for Electrical Characteristic Analysis of the Arrester of AC Filter[J]. Electric power, 2021, 54(7): 141-148.
黄学民, 邓俊文, 邓京, 等. 交流滤波器避雷器电气特性分析中不同仿真模型的影响[J]. 中国电力, 2021,54(7):141-148. DOI: 10.11930/j.issn.1004-9649.202006322.
Xuemin HUANG, Junwen DENG, Jing DENG, et al. Influence of Different Simulation Models for Electrical Characteristic Analysis of the Arrester of AC Filter[J]. Electric power, 2021, 54(7): 141-148. DOI: 10.11930/j.issn.1004-9649.202006322.
交流滤波器是直流输电系统的重要设备。主要分析仿真模型对交流滤波器用避雷器电气特性(过电压、电流和吸收能量)的影响,基于PSCAD电磁仿真程序,开展滤波器投入和交流滤波器母线接地故障下的建模及仿真计算。仿真结果表明:在交流滤波器投入工况下,采用单个滤波器大组模型(模型1)进行仿真时,在运滤波器的避雷器不动作,与实际情况不符;在滤波器投入及滤波器母线接地故障下,完整参数模型(模型3)中各组滤波器用避雷器过电压比原系统模型(模型2)和模型1降低可达21%,电流降低可达53%,但吸收能量升高可达56%。因此,若在绝缘设计中不采用完整参数模型,避雷器电压电流设计值会偏大,能量设计值会偏小,同时会在滤波器投入工况下忽略同大组其他交流滤波器的避雷器动作情况。
AC filter is an important equipment in DC transmission system. This paper mainly analyzes the influence of simulation model on the electrical characteristics (overvoltage
current and absorbed energy) of the arresters for AC filter
and carries out the modeling and simulation calculation for the filter input and AC filter bus grounding fault based on PSCAD electromagnetic simulation program. The simulation result shows that when the AC filter is put into operation and the traditional large group model for a single filter (model 1) was used for simulation
the arresters of the working filters did not act
which is different from the actual situation; under the filter input and filter bus grounding fault
the overvoltage of the arrester of each group of filters in complete parameter model (model 3) was lowered by 21% compared to that in the original system model (model 2) and model 1
and the current was reduced by up to 53%
but the absorbed energy increased by up to 56%. Therefore
if the complete parameter model is not used in the insulation design
the voltage and current design value of the arrester could be too large while the energy design value could be too small. At the same time
the action of the arresters of other AC filters in the same group could be easily ignored when the filter is put into operation.
王璐璐, 曹野. 高压直流输电技术综述[J]. 科学技术创新, 2018(10): 50–51.
WANG Lulu, CAO Ye. Summary of HVDC transmission technology[J]. Scientific and Technological Innovation, 2018(10): 50–51.
古智鹏. 换流站交流滤波器电容器运维分析及故障处理[J]. 电力电容器与无功补偿, 2019, 40(6): 58–61.
GU Zhipeng. Operation&maintenance analysis and fault treatment on AC filter capacitor at converter station[J]. Power Capacitor&Reactive Power Compensation, 2019, 40(6): 58–61.
严伟, 秦金锋, 叶志良, 等. 从西站交流滤波器投入导致直流电压跌落分析[J]. 广东电力, 2019, 32(4): 41–47.
YAN Wei, QIN Jinfeng, YE Zhiliang, et al . Analysis of DC voltage drop caused by AC filter input in congxi converter station[J ] . Guangdong Electric Power, 2019, 32(4): 41–47.
CHEN C F, HAN Y X, LIU J X, et al . Research on the lightning intruding overvoltage and protection measures of 500 kV AC fault current limiter[J ] . Energies, 2019, 12(20): 3845.
HAN Y X, ZHANG Y Q, RUAN Y X, et al . Study on influencing factors of insulators flashover characteristics on the 110 kV true tower under the lightning impulse[J ] . IEEE Access, 2018, 6(10): 66536–66544.
李歆蔚. ±800 kV换流站交流滤波器过电压及绝缘配合研究[D]. 广州: 华南理工大学, 2019.
LI Xinwei. Research on overvoltage and insulation coordination of the AC filter in ±800 kV converter station[D]. Guangzhou: South China University of Technology, 2019.
罗新, 黄学民, 刘春涛, 等. 换流站交流滤波器用避雷器频繁动作原因分析[J]. 电瓷避雷器, 2019(3): 159–164.
LUO Xin, HUANG Xuemin, LIU Chuntao, et al . Analysis of reasons for the frequent action of arrester in AC filter in converter station[J ] . Insulators and Surge Arresters, 2019(3): 159–164.
罗新, 刘浩, 黄学民, 等. ±800 kV糯扎渡直流工程交流滤波器合闸超前相位对避雷器动作情况影响分析[J]. 广东电力, 2018, 31(6): 133–138.
LUO Xin, LIU Hao, HUANG Xuemin, et al . Analysis on effect of closing phase of AC filter of ±800 kV nuozhadu DC transmission project on arrester action[J ] . Guangdong Electric Power, 2018, 31(6): 133–138.
LUO X, HUANG X M, LIU C T, et al . The influence of the closing phase angle of AC filter on the action of arrester in ±800 kV Nuozhadu DC transmission project[J ] . Advances in Mechanical Engineering, 2020, 12(2): 1–8.
张杰. 电感型避雷针提高输电线路反击耐雷性能机理研究[D]. 广州: 华南理工大学, 2017.
ZHANG Jie. Study on mechanism of improving the lighting protection performance of back-flashover due to inductive lightning rod[D]. Guangzhou: South China University of Technology, 2017.
李海明. 基于电磁场理论的电感型避雷针防雷机理研究[D]. 广州: 华南理工大学, 2015.
LI Haiming. Study on lightning protection mechanism of anti-lightning rod based on electromagnetic field theory[D]. Guangzhou: South China University of Technology, 2015.
牛犁, 贺明, 熊斌宇. 换流阀杂散电容计算及其对MMC电压应力水平的影响[J]. 智慧电力, 2019, 47(11): 104–109.
NIU Li, HE Ming, XIONG Binyu. Calculation of stray capacitance in converter valve and its influence on MMC voltage stress[J]. Smart Power, 2019, 47(11): 104–109.
郭焕, 汤广福, 查鲲鹏, 等. 直流输电换流阀杂散电容和冲击电压分布的计算[J]. 中国电机工程学报, 2011, 31(10): 116–122.
GUO Huan, TANG Guangfu, ZHA Kunpeng, et al . Calculation on stray capacitances and impulse voltage distribution of HVDC converter valve[J ] . Proceedings of the CSEE, 2011, 31(10): 116–122.
孙海峰, 崔翔, 齐磊, 等. 高压直流换流阀过电压分布及其影响因素分析[J]. 中国电机工程学报, 2010, 30(22): 120–126.
SUN Haifeng, CUI Xiang, QI Lei, et al . Overvoltage distribution in HVDC converter valves and analysis of influencing factors[J ] . Proceedings of the CSEE, 2010, 30(22): 120–126.
姚勇, 王建, 顾德文, 等. 基于场路模型的500 kV变电站母线避雷器杂散电容干扰电流的计算[J]. 电瓷避雷器, 2018(5): 59–64.
YAO Yong, WANG Jian, GU Dewen, et al . Calculation of stray capacitance interference current of busbar arrester in 500 kV substation based on field circuit model[J ] . Insulators and Surge Arresters, 2018(5): 59–64.
玉素娇. 直流输电系统中不同类型交流滤波器投切冲击电流研究[J]. 电工技术, 2017(11): 52–53,63.
YU Sujiao. Research on switching impulse current of different types of AC filters in HVDC system[J]. Electric Engineering, 2017(11): 52–53,63.
但刚, 李明, 杨俊. ±660 kV宁东-山东直流输电工程交流滤波器暂态额定值计算[J]. 高电压技术, 2010, 36(6): 1583–1588.
DAN Gang, LI Ming, YANG Jun. Transient rating calculation of AC filters in ±660 kV HVDC transmission project from ningdong to Shandong[J]. High Voltage Engineering, 2010, 36(6): 1583–1588.
马春, 李明, 曹燕明. ±800 kV锦屏—苏南特高压直流输电工程交流滤波器暂态额定值计算[J]. 电力建设, 2012, 33(12): 32–36.
MA Chun, LI Ming, CAO Yanming. Transient rated calculation of AC filters in ±800 kV jinpin-Sunan UHV DC power transmission project[J]. Electric Power Construction, 2012, 33(12): 32–36.
李山, 杨定乾. 某换流站750 kV交流滤波器投切仿真计算及现场实测分析[J]. 电力电容器与无功补偿, 2020, 41(1): 91–95, 101.
LI Shan, YANG Dingqian. Simulated calculation and measurement analysis on switching of 750 kV AC filter at converter station[J]. Power Capacitor&Reactive Power Compensation, 2020, 41(1): 91–95, 101.
谢丰战, 韦翠琼, 陈超兮, 等. 基于PSCAD的特高压直流输电系统单相接地过电压的研究[J]. 电气开关, 2014, 52(6): 61–64.
XIE Fengzhan, WEI Cuiqiong, CHEN Chaoxi, et al . Research on overvoltage caused by single-phase grounding on UHVDC transmission system based on PSCAD[J ] . Electric Switchgear, 2014, 52(6): 61–64.
杨勇, 张静, 杨智, 等. 特高压直流输电系统交流滤波器电容元件击穿故障仿真研究[J]. 电力电容器与无功补偿, 2018, 39(4): 1–6.
YANG Yong, ZHANG Jing, YANG Zhi, et al . Study on breakdown fault simulation for capacitor element of AC filter of UHVDC transmission system[J ] . Power Capacitor & Reactive Power Compensation, 2018, 39(4): 1–6.
罗新,邓俊文,邓京,等. 换流站交流滤波器用避雷器过电压仿真建模因素[J]. 南方电网技术, 2021, 15(2): 99–106.
LUO Xin, DENG Junwen, DENG Jing, et al . Modeling factors for overvoltage simulation of lightning arrester for AC filter in converter station[J ] . Southern Power System Technology, 2021, 15(2): 99–106.
苏宜靖, 董立, 唐律, 等. 柔性直流配电网过电压及避雷器配置研究[J]. 浙江电力, 2019, 38(3): 20–24.
SU Yijing, DONG Li, TANG Lv, et al . Research on overvoltage and arrester allocation in flexible DC distribution network[J ] . Zhejiang Electric Power, 2019, 38(3): 20–24.
罗晓晓. 特高压避雷器的结构设计及主要性能参数[J]. 河北电力技术, 2015, 34(6): 67.
张若愚,曹枚根,毛宇,等. 增设拉线对特高压直流复合避雷器地震响应的影响分析[J]. 南方电网技术, 2020, 14(4): 31–38.
ZHANG Ruoyu, CAO Meigen, MAO Yu, et al . Influence analysis of additional guy cable on the seismic response of UHVDC composite arrester[J ] . Southern Power System Technology, 2020, 14(4): 31–38.
0
浏览量
0
下载量
2
CSCD
关联资源
相关文章
相关作者
相关机构
京公网安备11010802024621