Fault Line Selection in Cooperation with Multi-Mode Grounding Control for Updates the Floating Nuclear Power Plant Grid
The Floating nuclear power plant grid is composed of power generation
in-station power supply and external power delivery. To ensure the safety of the nuclear island
the in-station system adopts a special power supply mode
while the external power supply needs to be adapted to different types of external systems. Because of frequent single phase-ground faults and various fault forms
the fault line selection protection should be accurate
sensitive and adaptive. This paper presents a fault line selection method in cooperation with multi-mode grounding control. Based on the maximum united energy entropy ratio (MUEER)
the optimal wavelet basis function and decomposition scale are adaptively chosen
while the fault line is selected by wavelet transform modulus maxima (WTMM). For high-impedance faults (HIFs)
to enlarge the fault feature
the system grounding mode can be switched by the multi-mode grounding control. Based on the characteristic of HIFs
the fault line can be selected by comparing phase differences of zero-sequence current mutation and fault phase voltage mutation before and after the fault. Simulation results using MATLAB/Simulink show the effectiveness of the proposed method in solving the protection problems.
Abstract
The Floating nuclear power plant grid is composed of power generation
in-station power supply and external power delivery. To ensure the safety of the nuclear island
the in-station system adopts a special power supply mode
while the external power supply needs to be adapted to different types of external systems. Because of frequent single phase-ground faults and various fault forms
the fault line selection protection should be accurate
sensitive and adaptive. This paper presents a fault line selection method in cooperation with multi-mode grounding control. Based on the maximum united energy entropy ratio (MUEER)
the optimal wavelet basis function and decomposition scale are adaptively chosen
while the fault line is selected by wavelet transform modulus maxima (WTMM). For high-impedance faults (HIFs)
to enlarge the fault feature
the system grounding mode can be switched by the multi-mode grounding control. Based on the characteristic of HIFs
the fault line can be selected by comparing phase differences of zero-sequence current mutation and fault phase voltage mutation before and after the fault. Simulation results using MATLAB/Simulink show the effectiveness of the proposed method in solving the protection problems.
关键词
Keywords
references
1. Li, Z. H. A. N. G., Zhoufeng, L. I. U., Bocai, D. I. N. G., ( 2017 ). Design essentials of power system at offshore nuclear power platform[J ] . Marine Electric Electronic Engineering , 37 ( 11 ), 36–37.
2. Yunchao, W. A. N. G., Zhanqing, Y. U., Jinliang, H. E., ( 2015 ). Performance of shipboard medium-voltage DC system of various grounding modes under monopole ground fault[J ] . IEEE Transactions on Industry Applications , 51 ( 6 ), 5002–5009.
3. Yunfeng, X. I. O. N. G., Shisheng, W. A. N. G., Wenqian, Z. H. A. N. G. ( 2012 ). A line-selection method of data fusion based on neural network[J ] . International Workshop on Information and Electronics Engineering , 29, 520–525.
4. Anbo, M. E. N. G., Jiafei, G. E., Deqiang, L. I., ( 2016 ). Research on fault line selection of distribution network using RBF neural network based on crisscross optimization algorithm optimization[J ] . Power System Protection and Control , 44 ( 21 ), 90–95.
5. Geethanjali, M., Priya, K. S. ( 2009 ). Combined wavelet transforms and neural network (WNN) based fault detection and classification in transmission lines[C ] . In Proceedings of International conference on control, automation, communication and energy conservation , Kongu Engn Coll, Perundurai, 4–6 June (pp. 1–7 ).
6. Zheng, Q. I. ( 2005 ). Research on technology of line detection and fault location for single-phase-to-earth in neutral point non-effectively grounded systems[D] . Beijing : North China Electric Power University.
8. Zhichao, L. I. N., Xinxing, L. I. U., Yingmin, W. A. N. G., ( 2018 ). Grounding fault protection based on zero sequence current comparison in low resistance grounding system[J ] . Power System Protection and Control , 46 ( 22 ), 15–21.
9. Rui, L. I. A. N. G., Lianhua, C. U. I., Zhili, D. U., ( 2014 ). Fault line selection and location in distribution power network based on traveling wave time difference of arrival relationships[J ] . High Voltage Engineering , 40 ( 11 ), 3411–3417.
10. Zhiyong, L. I., Wei, W. A. N. G., Liangwen, Z. H. U. A. N. G., ( 2019 ). Dynamic test of traveling wave line selecting device based on RTDS small time-step simulation[J ] . Power System Protection and Control , 47 ( 23 ), 108–114.
11. Mingming, X. U., Shuping, G. A. O., Zhongxue, C. H. A. N. G., ( 2018 ). Model recognition based single-phase earthed faulty line selection method of Petersen coil grounded system[J ] . Power System Protection and Control , 46 ( 2 ), 73–78.
12. Xinzhou, D. O. N. G., Shenxing, S. H. I. ( 2008 ). Identifying single-phase-to-ground fault feeder in neutral noneffectively grounded distribution system using wavelet transform[J ] . IEEE Transactions on Power Delivery , 23 ( 4 ), 1829–1837.
13. Sedighi, A. R., Haghifam, M. R., Malik, O. P., ( 2005 ). High impedance fault detection based on wavelet transform and statistical pattern recognition[J ] . IEEE Transactions on Power Delivery , 20 ( 4 ), 2414–2421.
14. MICHALIK, M., REBIZANT, W., LUKOWICZ, M., ( 2006 ). High impedance fault detection in distribution networks with use of wavelet based algorithm[J ] . IEEE Transactions on Power Delivery , 21 ( 4 ), 1793–1802.
15. Bin, W. A. N. G., Xin, C. U. I., Xinzhou, D. O. N. G. ( 2020 ). Overview of arc high impedance grounding fault detection technologies in distribution system[J ] . Proceedings of the CSEE , 40 ( 1 ), 96–107 377.
16. Baohui, Z. H. A. N. G., Zhiguo, H. A. O., Zhiqian, B. O. ( 2016 ). New development in relay protection for smart grid[J ] . Protection and Control of Modern Power Systems , 1 ( 2 ), 121–127. https://doi.org/10.1186/s41601–016-0025-x.
17. Zhiwei, C. H. E. N., Qin, S. H. U. ( 2015 ). Study on single phase ground fault location of mixed distribution network based on neural network and SVD[J ] . Digital Technology and Application , 11, 100–103.
18. Bianling, S. U. ( 2016 ). Application of wavelet transform in power system[M] (pp. 39–42 ). Beijing : Science Press.
19. Quan, P. A. N. G., Cuirong, Y. A. N. G., Yingle, F. A. N., ( 2007 ). Image segmentation based on the local minimum cross-entropy and quad-tree[C ] . In Proceedings of 5th International Conference on Wavelet Analysis and Pattern Recognition , Beijing, China (pp. 356–359 ).
20. Ray, P., Mishra, D. P., Mohaptra, S. ( 2016 ). Fault classification of a transmission line using wavelet transform fuzzy logic[C ] . In Proceedings of 1st IEEE International Conference on Power Electronics, Intelligent Control, and Energy Systems (ICPEICES) , Delhi, India, (pp. 1–6 ).
21. Xiaoqi, F. U. ( 2014 ). Research on the technology and application of 10 kV distribution network neutral grounding through small resistance[D] . Beijing : North China Electric Power University.