Rajaraman P., Sundaravaradan N.A., Mallikarjuna B., et al. Robust fault analysis in transmission linesusing Synchrophasor measurements[J]. Protection and Control of Modern Power Systems, 2018, 3(1).
Rajaraman P., Sundaravaradan N.A., Mallikarjuna B., et al. Robust fault analysis in transmission linesusing Synchrophasor measurements[J]. Protection and Control of Modern Power Systems, 2018, 3(1).DOI: 10.1186/s41601-018-0082-4.
Robust fault analysis in transmission linesusing Synchrophasor measurements
As more electric utilities and transmission system operators move toward the smart grid concept
robust fault analysis has become increasingly complex. This paper proposes a methodology for the detection
classification
and localization of transmission line faults using Synchrophasor measurements. The technique involves the extraction of phasors from the instantaneous three-phase voltages and currents at each bus in the system which are then decomposed into their symmetrical components. These components are sent to the phasor data concentrator (PDC) for real-time fault analysis
which is completed within 2–3 cycles after fault inception. The advantages of this technique are its accuracy and speed
so that fault information may be appropriately communicated to facilitate system restoration. The proposed algorithm is independent of the transmission system topology and displays high accuracy in its results
even with varying parameters such as fault distance
fault inception angle and fault impedance. The proposed algorithm is validated using a three-bus system as well as the Western System Coordinating Council (WSCC) nine bus system. The proposed algorithm is shown to accurately detect the faulted line and classify the fault in all the test cases presented.
Abstract
As more electric utilities and transmission system operators move toward the smart grid concept
robust fault analysis has become increasingly complex. This paper proposes a methodology for the detection
classification
and localization of transmission line faults using Synchrophasor measurements. The technique involves the extraction of phasors from the instantaneous three-phase voltages and currents at each bus in the system which are then decomposed into their symmetrical components. These components are sent to the phasor data concentrator (PDC) for real-time fault analysis
which is completed within 2–3 cycles after fault inception. The advantages of this technique are its accuracy and speed
so that fault information may be appropriately communicated to facilitate system restoration. The proposed algorithm is independent of the transmission system topology and displays high accuracy in its results
even with varying parameters such as fault distance
fault inception angle and fault impedance. The proposed algorithm is validated using a three-bus system as well as the Western System Coordinating Council (WSCC) nine bus system. The proposed algorithm is shown to accurately detect the faulted line and classify the fault in all the test cases presented.
Review of protection and fault handling fora flexible DC grid
Relay performance verification using faultevent records
Modeling methodology and faultsimulation of distribution networksintegrated with inverter-based D
Dual Alternative Iteration Algorithm-Based Hierarchical MPC Strategy for Frequency Regulation Control and Active Power Allocation of Wind-storage Coupling System
Real-Time Detection of Low-frequency Oscillations in Traction Power Supply Systems Based on Optimized Atomic Decomposition