Analysis of the Anti High-Altitude Electromagnetic Pulse Interference Ability of Relay Protection Devices
摘要
High altitude electromagnetic pulse (HEMP)
as a steep slope and high amplitude instantaneous energy shock
has stronger coupling and greater destructive power
which can easily cause the secondary control device of the substation to malfunction. In order to explore the anti-interference ability of the relay protection device to HEMP
a simulation model of electromagnetic radiation based on the actual physical structure was built
and the distribution characteristics of the electric field inside the device were explored under the influence of different excitation factors such as HEMP amplitude
incident angle
and polarisation direction. A radiation and conduction coupling test platform was built between the device and HEMP
and the HEMP threshold of the device malfunctioning due to radiated coupling interference was obtained by comparing the changes in the action characteristics of the device facing the same fault before and after irradiation. The tolerance of the device’s power port under HEMP-conducted interference is verified. The test results show that when the peak irradiation of HEMP reaches 35 kV/m
the device begins to malfunction
and the tripping time in the face of the same fault is significantly prolonged. The operational reliability of relay protection devices is greatly reduced
which affects the safe and stable operation of the power grid.
Abstract
High altitude electromagnetic pulse (HEMP)
as a steep slope and high amplitude instantaneous energy shock
has stronger coupling and greater destructive power
which can easily cause the secondary control device of the substation to malfunction. In order to explore the anti-interference ability of the relay protection device to HEMP
a simulation model of electromagnetic radiation based on the actual physical structure was built
and the distribution characteristics of the electric field inside the device were explored under the influence of different excitation factors such as HEMP amplitude
incident angle
and polarisation direction. A radiation and conduction coupling test platform was built between the device and HEMP
and the HEMP threshold of the device malfunctioning due to radiated coupling interference was obtained by comparing the changes in the action characteristics of the device facing the same fault before and after irradiation. The tolerance of the device’s power port under HEMP-conducted interference is verified. The test results show that when the peak irradiation of HEMP reaches 35 kV/m
the device begins to malfunction
and the tripping time in the face of the same fault is significantly prolonged. The operational reliability of relay protection devices is greatly reduced
which affects the safe and stable operation of the power grid.