Arash Abyaz, Mohammad Hamed Samimi, Amir Abbas Shayegani Akmal. Analysing the Impact of Frequency Bands on Partial Discharge Measurement Outcomes in Generators Through Model-Based Approach[J]. 高电压(英文), 2026,11(2).
Arash Abyaz, Mohammad Hamed Samimi, Amir Abbas Shayegani Akmal. Analysing the Impact of Frequency Bands on Partial Discharge Measurement Outcomes in Generators Through Model-Based Approach[J]. High Voltage, 2026, 11(2).
Arash Abyaz, Mohammad Hamed Samimi, Amir Abbas Shayegani Akmal. Analysing the Impact of Frequency Bands on Partial Discharge Measurement Outcomes in Generators Through Model-Based Approach[J]. 高电压(英文), 2026,11(2).DOI: 10.1049/hve2.70118.
Arash Abyaz, Mohammad Hamed Samimi, Amir Abbas Shayegani Akmal. Analysing the Impact of Frequency Bands on Partial Discharge Measurement Outcomes in Generators Through Model-Based Approach[J]. High Voltage, 2026, 11(2).DOI: 10.1049/hve2.70118.
Analysing the Impact of Frequency Bands on Partial Discharge Measurement Outcomes in Generators Through Model-Based Approach
摘要
The electromagnetic wave produced by a partial discharge (PD) covers a broad range of frequencies
from a few kHz to several 100 MHz. Because of the nonlinear response of the stator winding
each frequency component of the PD pulse experiences different levels of attenuation as it travels through the winding structure. Consequently
the choice of frequency band for PD measurement has a significant impact on the results obtained from these measurements. The measurement frequency band
along with other complexities in PD pulse propagation
adds to the challenge of interpreting the results of PD testing. Currently
there is no universally accepted threshold for harmful activities associated with PD in generators in any reputable standard. This article investigates the influence of the measurement frequency band on the results obtained from PD testing by utilising a comprehensive finite element model of a stator winding. The research findings indicate that measuring the PD apparent charge at lower frequencies
with a relatively wide bandwidth
provides results that are more closely related to the PD charge at its source.
Abstract
The electromagnetic wave produced by a partial discharge (PD) covers a broad range of frequencies
from a few kHz to several 100 MHz. Because of the nonlinear response of the stator winding
each frequency component of the PD pulse experiences different levels of attenuation as it travels through the winding structure. Consequently
the choice of frequency band for PD measurement has a significant impact on the results obtained from these measurements. The measurement frequency band
along with other complexities in PD pulse propagation
adds to the challenge of interpreting the results of PD testing. Currently
there is no universally accepted threshold for harmful activities associated with PD in generators in any reputable standard. This article investigates the influence of the measurement frequency band on the results obtained from PD testing by utilising a comprehensive finite element model of a stator winding. The research findings indicate that measuring the PD apparent charge at lower frequencies
with a relatively wide bandwidth
provides results that are more closely related to the PD charge at its source.
Low-Frequency Oscillation Suppression of FDR Time-Domain Diagnostic Waveforms for Cable Defects Based on Splicing Technology
Analysis of the Anti High-Altitude Electromagnetic Pulse Interference Ability of Relay Protection Devices
Review of Catenary Icing on High-Speed Railways: Characteristics, Impact and Countermeasures
A Novel Converter Transformer DAM-LSTNet Vibration Generation Model for Data Imbalance Identification
Enhancing Hydrophobic Stability of Silicone Rubber Insulators Under High-Voltage Direct Current Stress Through Optimised Nano-Fumed Silica Surface Area: A Dynamic Drop Test Study