Investigating New Approaches for Optimal Energisations of DC Cables: The Stepwise Energisation Technique
摘要
Abstract
This paper focuses on the energisation of high voltage DC (HVDC) and medium voltage DC (MVDC) insulation systems
referring mainly to cables for both theoretical development and validation testing. Cable system energisation can be frequent during its lifetime
and it can possibly be affected by partial discharges (PD)
because of manufacturing
laying
ageing
interfaces or structural cavities (as butt gaps). A theory-driven and measurement-based procedure is presented in this paper
having the purpose to minimise PD inception risk. This procedure is based on stepwise voltage application during cable energisation. The fundamental idea behind the proposed approach stems from considering that the jump voltage is the trigger of PD occurrence. Indeed
the jump voltage
and the consequent electric field variation
directly relates to AC PD inception voltage (PDIVAC). In addition
the electric field distribution in an insulation system is driven by insulation permittivity (capacitance) during voltage transients
and by conductivity in DC
thus the PDIVAC is generally smaller than DC PD inception voltage (PDIVDC). Hence
energising a DC cable by an initial step lower than PDIVAC
and then increasing the voltage in steps smaller than PDIVAC
would minimise the risk of PD inception during transients and the relevant degradation rate. However
this does not change
the risk of occurrence (if any) of low-repetition partial discharges at DC steady state. Effectiveness of the proposed technique is proved by the help of tests performed on cables with artificial surface and internal defects. It is shown that compared with the conventional energisation consisting of rapidly increasing voltage
the stepwise approach can reduce the risk of PD inception and related extrinsic ageing
even for the steady state voltages larger than PDIVDC.