Detection of trace CF4 in C4F7N-insulated gas-insulated metal-enclosed switchgear: Cascading specific chemical reactions with photoacoustic spectroscopy
|更新时间:2026-03-24
|
Detection of trace CF4 in C4F7N-insulated gas-insulated metal-enclosed switchgear: Cascading specific chemical reactions with photoacoustic spectroscopy
Detection of trace CF4 in C4F7N-insulated gas-insulated metal-enclosed switchgear: Cascading specific chemical reactions with photoacoustic spectroscopy
高电压(英文)2025年10卷第3期
作者机构:
State Key Laboratory of Electric Insulation and Power Equipment, Xi'an Jiaotong University,Xi'an,China
Zhicheng Wu, Jiahao Du, Zehao Zhang, 等. Detection of trace CF4 in C4F7N-insulated gas-insulated metal-enclosed switchgear: Cascading specific chemical reactions with photoacoustic spectroscopy[J]. 高电压(英文), 2025,10(3).
Zhicheng Wu, Jiahao Du, Zehao Zhang, et al. Detection of trace CF4 in C4F7N-insulated gas-insulated metal-enclosed switchgear: Cascading specific chemical reactions with photoacoustic spectroscopy[J]. High Voltage, 2025, 10(3).
Zhicheng Wu, Jiahao Du, Zehao Zhang, 等. Detection of trace CF4 in C4F7N-insulated gas-insulated metal-enclosed switchgear: Cascading specific chemical reactions with photoacoustic spectroscopy[J]. 高电压(英文), 2025,10(3). DOI: 10.1049/hve2.70049.
Zhicheng Wu, Jiahao Du, Zehao Zhang, et al. Detection of trace CF4 in C4F7N-insulated gas-insulated metal-enclosed switchgear: Cascading specific chemical reactions with photoacoustic spectroscopy[J]. High Voltage, 2025, 10(3). DOI: 10.1049/hve2.70049.
Detection of trace CF4 in C4F7N-insulated gas-insulated metal-enclosed switchgear: Cascading specific chemical reactions with photoacoustic spectroscopy
摘要
CF4 is a major decomposition product of the insulating gas in C4F7N-insulated gas-insulated metal-enclosed switchgear (GIS) during partial discharge or overheating faults. Its detection is essential for effective online monitoring and fault diagnosis of GIS. However
the application of photoacoustic spectroscopy for CF4 detection is hampered by significant cross-interference from the background C4F7N gas. In this paper
quantum chemical calculations revealed that C4F7N hydrolyses to form perfluoroisobutyrate and ammonia under base catalysis
exhibiting a low reaction energy barrier and high Gibbs free energy change
indicating ease of initiation and substantial reaction extent. This chemical specificity
unlike the stable CF4 which does not undergo such a reaction
enables selective purification of the gas to be detected through this hydrolysis reaction. Leveraging this insight
an experimental system was constructed that cascades chemical absorption purification with photoacoustic spectroscopy detection. This system effectively mitigates the cross-interference of C4F7N in CF4 detection by selectively absorbing C4F7N with over 95% efficiency through a base-catalysed nucleophilic hydrolysis reaction. This enabled the precise detection of trace amounts of CF4 against a substantial background of C4F7N with a detection limit reaching 14.79 μL/L. This advancement offers support for the online monitoring and fault diagnosis of eco-friendly GIS.
Abstract
CF4 is a major decomposition product of the insulating gas in C4F7N-insulated gas-insulated metal-enclosed switchgear (GIS) during partial discharge or overheating faults. Its detection is essential for effective online monitoring and fault diagnosis of GIS. However
the application of photoacoustic spectroscopy for CF4 detection is hampered by significant cross-interference from the background C4F7N gas. In this paper
quantum chemical calculations revealed that C4F7N hydrolyses to form perfluoroisobutyrate and ammonia under base catalysis
exhibiting a low reaction energy barrier and high Gibbs free energy change
indicating ease of initiation and substantial reaction extent. This chemical specificity
unlike the stable CF4 which does not undergo such a reaction
enables selective purification of the gas to be detected through this hydrolysis reaction. Leveraging this insight
an experimental system was constructed that cascades chemical absorption purification with photoacoustic spectroscopy detection. This system effectively mitigates the cross-interference of C4F7N in CF4 detection by selectively absorbing C4F7N with over 95% efficiency through a base-catalysed nucleophilic hydrolysis reaction. This enabled the precise detection of trace amounts of CF4 against a substantial background of C4F7N with a detection limit reaching 14.79 μL/L. This advancement offers support for the online monitoring and fault diagnosis of eco-friendly GIS.