Incident energy determination of three-phase arc flash using magnetohydrodynamics simulations: A case study for horizontal electrodes in open-air configurations
|更新时间:2026-03-24
|
Incident energy determination of three-phase arc flash using magnetohydrodynamics simulations: A case study for horizontal electrodes in open-air configurations
Incident energy determination of three-phase arc flash using magnetohydrodynamics simulations: A case study for horizontal electrodes in open-air configurations
高电压(英文)2025年10卷第2期
作者机构:
1. Smart Grids Institute, Federal University of Santa Maria, Santa Maria,Brazil
2. CPFL Energia, State Grid Brazil Holding S.A., Campinas,Brazil
Pedro O. Bacin, Mateus F. Fava, Rodolfo P. Londero, 等. Incident energy determination of three-phase arc flash using magnetohydrodynamics simulations: A case study for horizontal electrodes in open-air configurations[J]. 高电压(英文), 2025,10(2).
Pedro O. Bacin, Mateus F. Fava, Rodolfo P. Londero, et al. Incident energy determination of three-phase arc flash using magnetohydrodynamics simulations: A case study for horizontal electrodes in open-air configurations[J]. High Voltage, 2025, 10(2).
Pedro O. Bacin, Mateus F. Fava, Rodolfo P. Londero, 等. Incident energy determination of three-phase arc flash using magnetohydrodynamics simulations: A case study for horizontal electrodes in open-air configurations[J]. 高电压(英文), 2025,10(2). DOI: 10.1049/hve2.70009.
Pedro O. Bacin, Mateus F. Fava, Rodolfo P. Londero, et al. Incident energy determination of three-phase arc flash using magnetohydrodynamics simulations: A case study for horizontal electrodes in open-air configurations[J]. High Voltage, 2025, 10(2). DOI: 10.1049/hve2.70009.
Incident energy determination of three-phase arc flash using magnetohydrodynamics simulations: A case study for horizontal electrodes in open-air configurations
摘要
Abstract
Arc flashes pose significant hazards to personnel working with energised power lines due to their high thermal risk
quantified by incident energy (IE) in joules or calories per area. Accurate estimation of IE is crucial for ensuring safety. The most widely employed method for estimating IE from an arc flash is outlined in IEEE Std 1584-2018
which applies exclusively to three-phase AC arc flashes. However
limited research has explored alternative methods due to the complexities
costs
and preparation involved. Numerical simulations offer a viable alternative for studying arc flashes. This paper introduces a multiphysics simulation approach for determining IE by modelling three-phase AC arc flashes using the magnetohydrodynamics (MHD) theory. This study exclusively investigates horizontal electrodes in open-air (HOA) configuration due to the specific characteristics of the local power system configuration
which predominantly features overhead power lines
and the available test setup in the laboratory. The IE derived from simulations is compared with measurements from an arc flash laboratory based on IEEE Std 1584-2018 and with the IE calculated by the standard itself. The results indicate a significant alignment between this innovative approach and other methods for estimating IE for three-phase arc flashes.