An Enhanced Double Second-Order Generalised Integrator–Based Phase-Locked Loop Featuring Multisource Frequency Fusion and Adaptive Damping for Weak-Grid Conditions
|更新时间:2026-10-08
|
An Enhanced Double Second-Order Generalised Integrator–Based Phase-Locked Loop Featuring Multisource Frequency Fusion and Adaptive Damping for Weak-Grid Conditions
An Enhanced Double Second-Order Generalised Integrator–Based Phase-Locked Loop Featuring Multisource Frequency Fusion and Adaptive Damping for Weak-Grid Conditions
IET Energy Systems Integration2026年8卷第1期
作者机构:
1. School of Electronic Information and Automation, Hefei University,Anhui Province,Hefei,China
2. Zhengzhou University of Light Industry,Zhengzhou,China
Changzhou Yu, Wei Fang, Deyu Zhu, 等. An Enhanced Double Second-Order Generalised Integrator–Based Phase-Locked Loop Featuring Multisource Frequency Fusion and Adaptive Damping for Weak-Grid Conditions[J]. IET Energy Systems Integration, 2026,8(1).
Changzhou Yu, Wei Fang, Deyu Zhu, et al. An Enhanced Double Second-Order Generalised Integrator–Based Phase-Locked Loop Featuring Multisource Frequency Fusion and Adaptive Damping for Weak-Grid Conditions[J]. IET Energy Systems Integration, 2026, 8(1).
Changzhou Yu, Wei Fang, Deyu Zhu, 等. An Enhanced Double Second-Order Generalised Integrator–Based Phase-Locked Loop Featuring Multisource Frequency Fusion and Adaptive Damping for Weak-Grid Conditions[J]. IET Energy Systems Integration, 2026,8(1).DOI: 10.1049/esi2.70047.
Changzhou Yu, Wei Fang, Deyu Zhu, et al. An Enhanced Double Second-Order Generalised Integrator–Based Phase-Locked Loop Featuring Multisource Frequency Fusion and Adaptive Damping for Weak-Grid Conditions[J]. IET Energy Systems Integration, 2026, 8(1).DOI: 10.1049/esi2.70047.
An Enhanced Double Second-Order Generalised Integrator–Based Phase-Locked Loop Featuring Multisource Frequency Fusion and Adaptive Damping for Weak-Grid Conditions
摘要
Abstract
As the penetration rate of renewable energy represented by photovoltaic (PV) power in power systems continues to increase
the synchronisation stability of grid-connected inverters under weak-grid conditions faces severe challenges. The double second-order generalised integrator–based phase-locked loop (DSOGI-PLL)
a key technology for grid-connected control in weak grids
when significant fluctuations occur in grid frequency or voltage
its dynamic response and phase-tracking accuracy are significantly affected
even threatening the stable operation of the system. Analysis indicates that one of the key issues leading to the performance degradation of the DSOGI-PLL in weak grids is the lack of a fast and accurate frequency estimation. To address this
after comparing three frequency estimation methods—namely
the output frequency of the PLL itself
the grid-voltage zero-crossing detection frequency and the adaptive notch filter frequency—this paper proposes a multisource frequency fusion and adaptive damping DSOGI-PLL (MSFFAD-DSOGI-PLL). By analysing the harmonic content and frequency deviation of the power grid
the proposed method adaptively weight-fuses the results of the above three frequency estimation approaches and corrects the resonant centre frequency of the DSOGI in real time. On this basis
to balance the dynamic response and steady-state accuracy of the system under different operating conditions
an adaptive damping adjustment mechanism based on fuzzy logic linearisation is designed to achieve stable operation over a wide voltage/frequency range. Finally
experimental results demonstrate that compared with the traditional DSOGI-PLL
the proposed method exhibits stronger robustness and higher tracking accuracy under complex grid conditions such as large-range fluctuations in grid frequency and voltage.