Singular Perturbation and Complex Torque Analyses of Doubly Fed Induction Generator With Additional Inertia Control
|更新时间:2026-03-24
|
Singular Perturbation and Complex Torque Analyses of Doubly Fed Induction Generator With Additional Inertia Control
Singular Perturbation and Complex Torque Analyses of Doubly Fed Induction Generator With Additional Inertia Control
Energy Internet2025年2卷第2期
作者机构:
1. State Key Laboratory of HVDC (Electric Power Research Institute, Guangdong Provincial Key Laboratory of Intelligent Operation and Control for New Energy Power System, CSG Key Laboratory for Power System Simulation (Electric Power Research Institute, China Southern Power Grid), National Energy Power Grid Technology R&D Centre, China Southern Power Grid),Guangzhou,China
2. Contribution: Visualization, Supervision
3. Contribution: Validation, Data curation
4. State Key Laboratory of Advanced Electromagnetic Engineering and Technology School of Electrical and Electronic Engineering, Huazhong University of Science and Technology,Wuhan,China
Qi Guo, Jiawei Yu, Hongsheng Xu, 等. Singular Perturbation and Complex Torque Analyses of Doubly Fed Induction Generator With Additional Inertia Control[J]. Energy Internet, 2025,2(2).
Qi Guo, Jiawei Yu, Hongsheng Xu, et al. Singular Perturbation and Complex Torque Analyses of Doubly Fed Induction Generator With Additional Inertia Control[J]. Energy Internet, 2025, 2(2).
Qi Guo, Jiawei Yu, Hongsheng Xu, 等. Singular Perturbation and Complex Torque Analyses of Doubly Fed Induction Generator With Additional Inertia Control[J]. Energy Internet, 2025,2(2). DOI: 10.1049/ein2.70001.
Qi Guo, Jiawei Yu, Hongsheng Xu, et al. Singular Perturbation and Complex Torque Analyses of Doubly Fed Induction Generator With Additional Inertia Control[J]. Energy Internet, 2025, 2(2). DOI: 10.1049/ein2.70001.
Singular Perturbation and Complex Torque Analyses of Doubly Fed Induction Generator With Additional Inertia Control
摘要
Abstract
The doubly fed induction generator (DFIG) shows multi-time-scale and strong nonlinearity
making its stability analysis difficult. This paper conducts small perturbation stability analysis for the single-DFIG infinite-bus system with additional inertia control (AIC). First
the full-order electromagnetic transient model is constructed based on its topology and control structure. Then
the original model is reduced by using the singular perturbation method
and the validity of the simplified sixth-order model is verified by simulation. After linearising the sixth-order model based on the root locus and frequency response diagrams
it is found that increasing the gain coefficient Kf of the AIC could improve the inertia response characteristics but weaken the system's small disturbance stability. Furthermore
a complex torque model is constructed
which reveals that the system's negative damping originates from the terminal voltage control loop. Moreover
as Kf increases
the inherent damping continuously decreases
leading to further deterioration of the negative damping. As Tf increases
the stability of the system initially weakens and then strengthens. This study could help understand the DFIG grid-tied system dynamics.