Adaptive linear active disturbance-rejection control strategy reduces the impulse current of compressed air energy storage connected to the grid
Power Storage and Hydrogen Utilization Key Technologies|更新时间:2026-10-05
|
Adaptive linear active disturbance-rejection control strategy reduces the impulse current of compressed air energy storage connected to the grid
Adaptive linear active disturbance-rejection control strategy reduces the impulse current of compressed air energy storage connected to the grid
全球能源互联网(英文)2024年7卷第5期 页码:577-589
作者机构:
1. State Key Laboratory of Alternate Electrical Power System with Renewable Energy Sources, North China Electric Power University,Baoding,PR China,071003
2. State Grid Handan Electric Power Supply Company,Handan,China,056035
Jianhui Meng, Yaxin Sun, Zili Zhang. Adaptive linear active disturbance-rejection control strategy reduces the impulse current of compressed air energy storage connected to the grid[J]. 全球能源互联网(英文), 2024,7(5):577-589.
Jianhui Meng, Yaxin Sun, Zili Zhang. Adaptive linear active disturbance-rejection control strategy reduces the impulse current of compressed air energy storage connected to the grid[J]. Global Energy Interconnection, 2024, 7(5): 577-589.
Jianhui Meng, Yaxin Sun, Zili Zhang. Adaptive linear active disturbance-rejection control strategy reduces the impulse current of compressed air energy storage connected to the grid[J]. 全球能源互联网(英文), 2024,7(5):577-589.DOI: 10.1016/j.gloei.2024.10.001.
Jianhui Meng, Yaxin Sun, Zili Zhang. Adaptive linear active disturbance-rejection control strategy reduces the impulse current of compressed air energy storage connected to the grid[J]. Global Energy Interconnection, 2024, 7(5): 577-589.DOI: 10.1016/j.gloei.2024.10.001.
Adaptive linear active disturbance-rejection control strategy reduces the impulse current of compressed air energy storage connected to the grid
摘要
Abstract
The merits of compressed air energy storage (CAES) include large power generation capacity
long service life
and environmental safety. When a CAES plant is switched to the grid-connected mode and participates in grid regulation
using the traditional control mode with low accuracy can result in excess grid-connected impulse current and junction voltage. This occurs because the CAES output voltage does not match the frequency
amplitude
and phase of the power grid voltage. Therefore
an adaptive linear active disturbance-rejection control (A-LADRC) strategy was proposed. Based on the LADRC strategy
which is more accurate than the traditional proportional integral controller
the proposed controller is enhanced to allow adaptive adjustment of bandwidth parameters
resulting in improved accuracy and response speed. The problem of large impulse current when CAES is switched to the grid-connected mode is addressed
and the frequency fluctuation is reduced. Finally
the effectiveness of the proposed strategy in reducing the impact
of CAES on the grid connection was verified using a hardware-in-the-loop simulation platform. The influence of the
k
value in the adaptive- adjustment formula on the A-LADRC was analyzed through simulation. The anti-interference performance of the control was verified by increasing and decreasing the load during the presynchronization process.