Jie Tong, Yuanpeng Tan, Zhonghao Zhang, 等. Non-intrusive temperature rise fault-identification of distribution cabinet based on tensor block-matching[J]. 全球能源互联网(英文), 2023,6(3):324-333.
Jie Tong, Yuanpeng Tan, Zhonghao Zhang, et al. Non-intrusive temperature rise fault-identification of distribution cabinet based on tensor block-matching[J]. Global Energy Interconnection, 2023, 6(3): 324-333.
Jie Tong, Yuanpeng Tan, Zhonghao Zhang, 等. Non-intrusive temperature rise fault-identification of distribution cabinet based on tensor block-matching[J]. 全球能源互联网(英文), 2023,6(3):324-333.DOI: 10.1016/j.gloei.2023.06.006.
Jie Tong, Yuanpeng Tan, Zhonghao Zhang, et al. Non-intrusive temperature rise fault-identification of distribution cabinet based on tensor block-matching[J]. Global Energy Interconnection, 2023, 6(3): 324-333.DOI: 10.1016/j.gloei.2023.06.006.
Non-intrusive temperature rise fault-identification of distribution cabinet based on tensor block-matching
摘要
Abstract
In this study
a novel non-intrusive temperature rise fault-identification method for a distribution cabinet based on tensor block-matching is proposed. Two-stage data repair is used to reconstruct the temperature-field information to support the demand for temperature rise fault-identification of non-intrusive distribution cabinets. In the coarse-repair stage
this method is based on the outside temperature information of the distribution cabinet
using tensor block-matching technology to search for an appropriate tensor block in the temperature-field tensor dictionary
filling the target space area from the outside to the inside
and realizing the reconstruction of the three-dimensional temperature field inside the distribution cabinet. In the fine-repair stage
tensor super-resolution technology is used to fill the temperature field obtained from coarse repair to realize the smoothing of the temperature-field information inside the distribution cabinet. Non-intrusive temperature rise fault-identification is realized by setting clustering rules and temperature thresholds to compare the location of the heat source with the location of the distribution cabinet components. The simulation results show that the temperature- field reconstruction error is reduced by 82.42% compared with the traditional technology
and the temperature rise fault- identification accuracy is greater than 86%
verifying the feasibility and effectiveness of the temperature-field reconstruction and temperature rise fault-identification.
Modeling and clustering of residential electricity consumption for short-term forecasting using seasonal autoregressive integrated moving average (SARIMA)
Momentum vectorized adaptive DDPG-based PSC mitigator design for hybrid PV-TEG systems with auxiliary battery participation
Forecasting the average daily and during the hours of maximum electric load based on the data of the average monthly electricity consumption with single and other energy sources
Distribution network data asset protection considering multiple topology and multi-dimensional knowledge graph
Negative electricity prices in electricity markets: causes, impacts,and response strategies