Yanqiu Huang, Yirui Zhang, Shengnan Guo, 等. Spray field characteristics and the effect of spray-local exhaust ventilation on the control of high-temperature buoyant jets[J]. 能源与人工环境(英文), 2026,7(1):82-93.
Yanqiu Huang, Yirui Zhang, Shengnan Guo, et al. Spray field characteristics and the effect of spray-local exhaust ventilation on the control of high-temperature buoyant jets[J]. Energy and Built Environment, 2026, 7(1): 82-93.
Yanqiu Huang, Yirui Zhang, Shengnan Guo, 等. Spray field characteristics and the effect of spray-local exhaust ventilation on the control of high-temperature buoyant jets[J]. 能源与人工环境(英文), 2026,7(1):82-93. DOI: 10.1016/j.enbenv.2024.07.004.
Yanqiu Huang, Yirui Zhang, Shengnan Guo, et al. Spray field characteristics and the effect of spray-local exhaust ventilation on the control of high-temperature buoyant jets[J]. Energy and Built Environment, 2026, 7(1): 82-93. DOI: 10.1016/j.enbenv.2024.07.004.
Spray field characteristics and the effect of spray-local exhaust ventilation on the control of high-temperature buoyant jets
摘要
Abstract
Process equipment limitations resulted in constraints on the location of the exhaust hood
which in turn caused escape of high-temperature buoyant jets. In response to this situation
spray system is installed as an auxiliary measure to improve the control effect by spray cooling and weakening the momentum. However
the correlation between spray parameters and its atomization characteristics in high temperature ambient is not clear
reasonable spray parameters directly affect the performance of spray-local exhaust ventilation (SLEV). In this study
we discuss the spray field characteristics under the action of high-temperature buoyant jets
the effects of exhaust and spray parameters on the capture efficiency of SLEV
combined with orthogonal test to get the optimization order. Influences discussed include: exhaust velocity
spray pressure
and nozzle hole diameter. The results showed that SLEV provides superior control of high-temperature buoyant jets
up to two times that of the local exhaust ventilation (LEV). Compared to nozzle hole diameter
the spray pressure significantly effects spray field characteristics. Under high-temperature buoyant jets conditions
the statistical mean diameter obeys a power function relationship with spray pressure
and the capture efficiency was 75% as the spray pressure of 2.0 MPa and nozzle hole diameter of 1.8 mm. The factors affecting the performance of SLEV were found to be exhaust velocity spray pressure nozzle hole diameter by range analysis. The research results are expected to contribute to the optimization and enhancement of the SLEV.