SHUAI Yong, LI Yingwu, YANG Rong, et al. Mechanism analysis of 35 kV cable terminal discharge and troubleshooting method research[J]. 2016, 36(2): 91-94.
SHUAI Yong, LI Yingwu, YANG Rong, et al. Mechanism analysis of 35 kV cable terminal discharge and troubleshooting method research[J]. 2016, 36(2): 91-94.DOI:
35kV电缆终端放电及隐患排查方法分析
摘要
发生的一起35 k V电缆终端局部过热认为是电压致热性危急缺陷。停电解体检查发现因工艺问题使半导体出现尖端
The overheating defects of 35 k V cable terminal were found by infrared temperature precision measurement which were determined as voltage pyrogenic critical defects. The fault reason is a partial discharge caused by poor processing technology leading to partial charge and cable overheating. Previous failures of cable terminal were analyzed comprehensively
the standpoint that the key of cable installation quality is the quality of the cable stress cone is put forward. The key quality points of stress cone installation position is explained by net-vibes shrink terminal
and the several common project cable terminal extension program and the troubleshooting method of transport cable terminal stress cone installation process is recommended.