To address the insufficient dispatch feasibility caused by the mismatch between cyber-layer optimization decisions and physical-layer nonlinear responses in a power-steam cogeneration system
a multi-time-scale coordinated optimal dispatch method based on cyber-physical decoupling is proposed. Firstly
a nonlinear mechanism model is established by considering the load rate-temperature coupled efficiency of the proton exchange membrane fuel cell
auxiliary power consumption
start-up hysteresis
thermal inertia of the cooling loop
and the dynamic coefficient of performance of the heat pump. This model is used to describe the response deviation of dispatch commands during physical execution. In the day-ahead stage
forecast data are used as the baseline
and candidate dispatch schemes are generated using conservative parameters and random intensity. The operation regret
energy self-sufficiency rate
and photovoltaic utilization rate are then evaluated using the mechanism model to select the day-ahead baseline dispatch scheme. In the intra-day stage
flexible interval tracking is used to correct real-time source-load fluctuations and physical response deviations in a rolling manner. The results show that ignoring the nonlinear dynamic characteristics of key equipment leads to high-frequency energy storage regulation
unplanned external energy purchase
and photovoltaic curtailment. Compared with the traditional model predictive control strategy
the proposed method reduces the battery aging cost
curtailment penalty
and total operating cost by 54.09%
21.82%
and 4.01%
respectively. In 200 random disturbance scenarios
the median total operating cost is reduced by 5.12%
and the median photovoltaic utilization rate remains at 93.38%. These results verify that considering physical-layer nonlinear responses is necessary for improving dispatch feasibility.