In order to enhance the adaptability of the forced draft fan under deep peak shaving of a certain 350 MW supercritical unit and optimize the oxygen regulation capacity of the boiler operation under low-load conditions
the forced draft fan is subjected to speed reduction and optimization transformation.It carries out relevant tests on the actual performance of the forced draft fan after its renovation
and based on the test data and results
it analyzes and studies the effect of this forced draft fan renovation.The results show that the output margin of the forced draft fan after the transformation can meet the operation requirements of the full-load section of the unit.The operating points of the fans under different loads are far from the stall line
and there is no risk of stall.The regulation capacity of the boiler flue gas system operation under deep peak shaving is enhanced.It increases the efficiency of the fan