Optimal sizing and siting of distributed photovoltaic in distribution network considering coordinated optimization of reactive power compensation devices
Zhang Yi, Chu Tianze, WU Baojiang. Optimal sizing and siting of distributed photovoltaic in distribution network considering coordinated optimization of reactive power compensation devices[J]. 2026, 63(9).
Zhang Yi, Chu Tianze, WU Baojiang. Optimal sizing and siting of distributed photovoltaic in distribution network considering coordinated optimization of reactive power compensation devices[J]. 2026, 63(9).DOI:
A method for optimal sizing and siting of distributed photovoltaic and energy storage in a distribution network
considering coordinated optimization of reactive power compensation devices
is proposed to address issues such as voltage quality degradation
increased network losses
and reduced photovoltaic absorption capacity caused by improper location and capacity planning of distributed photovoltaic and energy storage.This method first determines the grid connection locations of distributed photovoltaic and energy storage based on network loss sensitivity and dynamic voltage stability index.Subsequently
a collaborative optimization configuration is employed utilizing distributed photovoltaic
energy storage
capacitor banks
and static var compensators
constructing a source-network-storage collaborative optimization bi-level planning model to determine the configuration capacity of distributed photovoltaic and energy storage. Furthermore
to effectively solve this bi-level model
the upper and lower models are transformed into a single-level model through associative modeling
followed by transforming this single-level model into a mixed integer second-order cone programming model using second-order cone relaxation and the Big-M method. Four scenarios are set up for simulation on the IEEE 33-node distribution system. The results indicate that the location and capacity of distributed photovoltaic and energy storagein the distribution network are determined using this method
not only is the photovoltaic absorption capacity and voltage quality improved