As an important component of primary equipment in substations
the abnormal heating of high voltage isolation switches would have adverse effects on their operational performance.To study the temperature field characteristics of high voltage isolation swi-tches under the coupling of multiple physical fields
taking the 110 kV GW55-126D high voltage isolation switch in a substation as an example
it establishes a finite element simulation model using COMSOL Multiphysics.It verifies the validity of the simulation model by the actual temperature measurement results in field operation.The result of research shows that the temperature field of the high voltage isolation switch tends to stabilize after 2000 s.For the temperature field of the contact finger