HUANG Yongrui. Suppression of AC overvoltage at sending end under DC transmission system fault based on controllable energy dissipation[J]. 2025, 44(4): 138-146.
HUANG Yongrui. Suppression of AC overvoltage at sending end under DC transmission system fault based on controllable energy dissipation[J]. 2025, 44(4): 138-146.DOI:
In the conventional high voltage direct current transmission system with large-scale new energy access
when commutation failure or DC blocking occurs at the receiving end
the reactive power surplus at the sending converter station may cause overvoltage in the AC system. In order to suppress the overvoltage at the sending end
an overvoltage suppression device is proposed based on the principle of controllable energy dissipation. Firstly
the overvoltage mechanism in weak AC system under the fault of DC system is analyzed
and the topology and working principle of the controllable energy dissipation device are proposed. Secondly
the suppression effect and electrical stress of the controllable dissipation device on AC system overvoltage under typical fault conditions is simulated and studied. Then
the design of the controllable dissipation device is carried out
focusing on the potential distribution of the arrester and the the static and dynamic characteristics of electromagnetic repulsion of the trigger switch under different coil turns
the entry and exit control strategy of the dissipation device is proposed. Finally
the experimental verification of the energy dissipation device prototype is carried out
proving the correctness of the design. The energy dissipation device developed is successfully applied to the ±800 kV Lu-Gu high voltage direct current transmission project
and the operation results show that the controllable energy dissipation device can effectively suppress of AC overvoltage.