WEN Xiankui. Interaction effect analysis of distributed photovoltaic access to distributed network based on single-port reduced model[J]. 2025, 44(4): 187-196.
WEN Xiankui. Interaction effect analysis of distributed photovoltaic access to distributed network based on single-port reduced model[J]. 2025, 44(4): 187-196.DOI:
A high penetration photovoltaic distribution network contain numerous voltage-sensitive power electronic devices
which effect with each other
increasing the computational complexity of the node grid-connected critical capacity. Therefore
an analytical method for calculating the grid-integration capacity of distributed photovoltaic devices at feeder injection points is proposed
using a single-port reduced-order model
while analyzing the interactions effect between connected devices and the injection point. Firstly
based on the current injection balance equation of the distribution network
the grid characteristic function is defined to characterize the nonlinear relationship between the current and voltage at the infeed point. A single-port reduced model is used to simplify the grid characteristic function to reduce the computational complexity. Then
the equivalent parameters of the model are calculated by selecting some specific cross-sections of the grid characteristic function. The grid-connected critical capacity expression at the infeed point and quantify the interaction effect is analytically derived. Finally
a case study on the IEEE 33-node distribution network shows that the grid-connected critical capacity is improved to a greater extent when the photovoltaic equipment is connected to the adjacent location of the infeed point. Among the different distribution network topologies
radial distribution network has the strongest effect of access equipment with the infeed point
followed by the ring distribution network and the smallest in the two-terminal power distribution network.