Variable speed pumped storage units have obvious advantages in efficiency and adaptability under various operation conditions compared with traditional fixed-speed pumped storage units. Since the full-power converter is the key equipment in variable speed pumped storage units
it is of great significance to study the application of various inverter topologies in large capacity variable speed pumped storage units. Taking a 100-MW-scale variable speed pumped storage unit as an example
based on the existing devices
an evaluation index system is constructed from the aspects of cost
loss
volume
etc.
and entropy method is used to weight the indexes. Four topologies are compared and analyzed in the design of the high-power variable speed pumped storage units with access voltage of 13.8 kV
including back-to-back three-level neutral point clamped (NPC) converter
back-to-back modular multilevel converter (MMC) and modular multilevel matrix converter (M3C). The results show that the cost of back-to-back MMC is the lowest
the overall efficiency of M3C is the highest
and the occupation space of M3C is the smallest. In summary
back-to-back MMC and M3C are two preferred solutions for the full power converter of 100-MW-scale variable speed pumped storage units.