Numerical simulation based cold tests for a tangentially fired boilerNumerical simulation based cold tests for a tangentially fired boiler
热能科学研究|更新时间:2025-09-28
|
Numerical simulation based cold tests for a tangentially fired boilerNumerical simulation based cold tests for a tangentially fired boiler
Numerical simulation based cold tests for a tangentially fired boiler
热力发电2012年41卷第12期 页码:19-24
作者机构:
1. School of Energy Science and Engineering,Central South University
2. Hunan Chemical Vacational Technology College
作者简介:
基金信息:
DOI:
中图分类号:
纸质出版:2012
稿件说明:
移动端阅览
XIANG Yuhua, ZHANG Jiayuan, ZHANG Xiaohui. Numerical simulation based cold tests for a tangentially fired boilerNumerical simulation based cold tests for a tangentially fired boiler[J]. 热力发电, 2012,41(12):19-24.
XIANG Yuhua1, 2, ZHANG Jiayuan1. Numerical simulation based cold tests for a tangentially fired boiler[J]. Thermal power generation, 2012, 41(12): 19-24.
XIANG Yuhua, ZHANG Jiayuan, ZHANG Xiaohui. Numerical simulation based cold tests for a tangentially fired boilerNumerical simulation based cold tests for a tangentially fired boiler[J]. 热力发电, 2012,41(12):19-24.DOI:
XIANG Yuhua1, 2, ZHANG Jiayuan1. Numerical simulation based cold tests for a tangentially fired boiler[J]. Thermal power generation, 2012, 41(12): 19-24.DOI:
Numerical simulation based cold tests for a tangentially fired boilerNumerical simulation based cold tests for a tangentially fired boiler
摘要
Such problems as flameout and serious slagging frequently occurred in a 170 t/h tangentially fired boiler burning inferior coals and with low load.Thus
cold tests were carried out to comprehensively investigate the performance of each air tube and the size and position of the tangential circle.Therefore
the cause and area of slagging in furnace can be determined.Thus
by numerical simulation on combustion
the optimal operation parameters for the boiler burning different coals under various loads conditions can be provided.The actual application showed that
the boiler fed with present coal can be long-term operated stably at 60% load
and its heat efficiency was up to 91%.Moreover
the abnormal flameout no longer occurred
and the slagging was alleviated a lot.
Abstract
Such problems as flameout and serious slagging frequently occurred in a 170 t/h tangentially fired boiler burning inferior coals and with low load.Thus
cold tests were carried out to comprehensively investigate the performance of each air tube and the size and position of the tangential circle.Therefore
the cause and area of slagging in furnace can be determined.Thus
by numerical simulation on combustion
the optimal operation parameters for the boiler burning different coals under various loads conditions can be provided.The actual application showed that
the boiler fed with present coal can be long-term operated stably at 60% load