The application of ABB UVISOR flame detecting system on boilers of 2×300 MW units in Henan Huarun Dengfeng Power Plant has been presented.Directing against the problems occurred in boiler operation
such as slagging on burners affecting the line of vision from flame-detecting probe
decreasing volatile content in fuel coal and low temperature of the primary air leading to lengthening the black zone of combustion etc.
an optimization debugging has been carriedout for this flame detecting system.The optimization debugging shows that the said flame detecting system can more excellently satisfy the requirements in operation
if the automatic optimizing function of four-set parameters in MFD can be used
introducing the function of automatically calling different parameters into the system according to different loads.