HE Shun-sheng Guangzhou Power Plant Co Ltd. ANALYSIS OF ELECTROMAGNETIC INTERFERENCE CAUSED BY FREQUENCY CONVERTER AND DISPOSAL THEREOF[J]. Thermal power generation, 2009, 38(5): 108-110.
HE Shun-sheng Guangzhou Power Plant Co Ltd. ANALYSIS OF ELECTROMAGNETIC INTERFERENCE CAUSED BY FREQUENCY CONVERTER AND DISPOSAL THEREOF[J]. Thermal power generation, 2009, 38(5): 108-110.DOI:
Directing against the problem of electromagnetic interference caused by the frequency converter of pulverized coal feeder to boilers of unit no.1 in Guangzhou Power Plant Co Ltd
the abnormal phenomenon of large fluctuation in analog output current and voltage signals coming from neighbouring sensitive equipments has been analysed.It is believed that the poor anti-interference capability of said frequency converter was caused by improper installation technology in the field
and retrofit measures
such as strengthening isolation
shielding
and grounding
etc.
have been put forward.After implementation
the operation of said frequency converter is stable
having remarkable electromagnetic interference resistant effectiveness.