OPERATIONAL CHARACTORS OF BOILERS EQUIPPED FOR ULTRA-SUPERCRITICAL 660 MW UNIT AFTER COMBINING THE BOOSTER AIR FAN IN DESULPHURIZATION SYSTEM AND THE INDUCED DRAFT FAN INTO ONE
CHEN Xing, ZHOU Liguo Datang Xinyang Hua'yu Power Generation Co Ltd. OPERATIONAL CHARACTORS OF BOILERS EQUIPPED FOR ULTRA-SUPERCRITICAL 660 MW UNIT AFTER COMBINING THE BOOSTER AIR FAN IN DESULPHURIZATION SYSTEM AND THE INDUCED DRAFT FAN INTO ONE[J]. Thermal power generation, 2010, 39(5): 85-86.
CHEN Xing, ZHOU Liguo Datang Xinyang Hua'yu Power Generation Co Ltd. OPERATIONAL CHARACTORS OF BOILERS EQUIPPED FOR ULTRA-SUPERCRITICAL 660 MW UNIT AFTER COMBINING THE BOOSTER AIR FAN IN DESULPHURIZATION SYSTEM AND THE INDUCED DRAFT FAN INTO ONE[J]. Thermal power generation, 2010, 39(5): 85-86.DOI:
The disasters occurred on boilers of ultra-supercritical 660 MW unit after combining the booster air fan and the induced draft fan into one in one power plant
such as leading to boiler trip
too low suction in furnace after boiler shutdown
resulting in deformation and tear of expansion joint connecting the induced draft fan and the electrostatic precipitator
etc.
have been analysed.For these
a test of suction variation in the furnace and effectiveness of automatic regulation for the induced draft fan after outfire of boiler should be carried out during the time of low load in debugging period has been put forward for the designed boiler of combining the booster air fan and the induced draft fan into one
and during the time of type-selection in design
selection of the air fans with too steep characteristic curves should be avoided.