ZHU Jienan1, WU Yongcun1, JIN Qilin2, et al. DESIGN AND APPLICATION OF A NEW BYPASS CONTROL STRATEGY FOR UNITS[J]. Thermal power generation, 2010, 39(9): 81-84.
ZHU Jienan1, WU Yongcun1, JIN Qilin2, et al. DESIGN AND APPLICATION OF A NEW BYPASS CONTROL STRATEGY FOR UNITS[J]. Thermal power generation, 2010, 39(9): 81-84.DOI:
Directing against the problems existing in many power plants
i.e.the bypass system of units is unable to bring its protective effects into full play
and only used as a drain valve of boiler and steam turbine in the stage of start-up or shutdown of units
a new bypass control strategy has been designed
which devides the HP-bypass into five control modes
the whole process automatic control of bypass system
from start-up of unit to connet the unit onto power grid
and returned again to sectionalization and shutdown of boiler
can be realized.Through calculation of steam's enthalpy drop before and after the LP-bypass system
the quantity of desuperheating water required by the LP-pass system can be precisely pre-estimated
thereby the exhaust steam from the LP-bypass system can be ensured to satisfy the requirement in operation of condenser.The above-mentioned control strategy has been applied onto an ultra-supercritical 1 000 MW unit in second-phase project of Ninghai Power Plant
the fast cut back (FCB) of unit without boiler shutdown being realized;after finishing assessment test of the bypass system
the unit is reconnected onto the power grid within 0 min
and the load of unit being increased to 480 MW after 15 min.