YANG Yongbo1, DUAN Kening1, JIANG Jianzhong2, et al. RETROFIT OF PLATEN REHEATER FOR 480t/h CFB BOILER[J]. Thermal power generation, 2010, 39(10): 73-76.
YANG Yongbo1, DUAN Kening1, JIANG Jianzhong2, et al. RETROFIT OF PLATEN REHEATER FOR 480t/h CFB BOILER[J]. Thermal power generation, 2010, 39(10): 73-76.DOI:
of thermal power plant subordinated to China Salt Jilantai Chlorine-Alkali Chemical Co Ltd
have been presented
it is believed that the main causes leading to deformation of the platen reheater are as follows:defects existing on oxpansion joint of the wall-entrance sealing box at top of the platen reheater constructed according to the original design;insufficent pretightening load applied to the constant force spring hanger of said hanging platen reheater;the guide means weren't installed for the outlet header of platen reheater;overtemperature phenomenon occurred on tube-wall of the platen reheater etc..Through retrofitting
the deformation of platen reheater can be controlled
the failures of tube-burst and boiler shutdown haven't occurred again