WANG Songling, ZHANG Lina, ZHANG Xuelei College of Energy and Power Engineering. DESIGN OF HEAT-PIPE TYPE INLET AIR COOLING SYSTEM FOR GAS TURBINES AND PERFORMANCE ANALYSIS THEREOF[J]. Thermal power generation, 2010, 39(9): 39-44.
WANG Songling, ZHANG Lina, ZHANG Xuelei College of Energy and Power Engineering. DESIGN OF HEAT-PIPE TYPE INLET AIR COOLING SYSTEM FOR GAS TURBINES AND PERFORMANCE ANALYSIS THEREOF[J]. Thermal power generation, 2010, 39(9): 39-44.DOI:
燃气轮机热管型进气冷却系统的设计及性能分析
摘要
针对燃气-蒸汽联合循环(联合循环)机组出力随环境温度升高而下降的问题
设计了1种新型燃气轮机(燃机)进气冷却系统
即利用热管型溴化锂吸收式制冷机(溴冷机)回收余热锅炉排烟余热制冷
以降低燃机进气温度。对余热锅炉排烟(简称排烟)流量及温度变化对联合循环机组性能影响的分析表明
加装热管型溴冷机的燃机进气冷却系统可使燃机进气温度下降10~15℃
联合循环机组年净增发电量约20000MW.h。在环境温度一定的条件下
随着排烟温度的增加
燃机进气温降幅度也不断增加。
Abstract
Directing against the problem of output capacity of the gas-steam combined cycle unit decreases as the ambient temperature rises
a new type inlet air cooling system of said unit has been designed by using the heat pipe type lithium bromide absorption chiller to recover the residual heat of flue gas dischargel from the waste heat boiler for refrigeration
so as to decrease lnlet air temperature for entering into the gas turbine.The analysis of influence of the flow rate and temperature variation for flue gas discharged from the waste heat boiler upon performance of the combined cycle unit shows that the inlet air cooling system equipped with bromide chiller can make the inler air temperature of the said gas turbine to decrease 10~15 ℃
the net annual electricity generation increases 20 000 MW·h.Under condition of constant ambient temperature
along with increasing of the discharged flue gas temperature
the temperature drop range of the inlet air entering into the gas turbine will also increase.